Installation – Flowserve AK 45 User Manual

Page 10

Advertising
background image

0

Installation

AK 45

Install the AK so that discharge is to open drain (without back pressure), preferably in a vertical line

with downwards flow.
The AK 45 can be installed in any plane with flow in the direction of the arrow. When the valve is

installed in a horizontal line, the cover must be on top.
If it is necessary to install the AK 45 in a horizontal line, the pipe on the discharge of the trap should

include a 90° downwards bend,

Fig. 3, Fig. 4.

Flanged design

. Observe position of installation.
. Observe flow direction. The flow direction arrow is located on the valve body.
. Leave at least

40 mm free space around the equipment for subsequent disassembly of the

cover

E.

4. Remove plastic plugs. They are

only used for transit protection.

5. Clean gasket surfaces of the two flanges.
6. Install condensate drain valve.

Screwed design

. Observe position of installation.
. Observe flow direction. The flow direction arrow is located on the valve body.
. Leave at least

40 mm free space around the equipment for subsequent disassembly of the

cover

E.

4. Remove plastic plugs. They are

only used for transit protection.

5. Clean internal threads.
6. Install condensate drain valve.