System malfunctions – Flowserve NRS 1-42 User Manual

Page 18

Advertising
background image

18

System Malfunctions

– continued –

The terminal strip of the NRS 1-42 is live during operation.
This presents the danger of electric shock.
Cut off power supply before mounting or removing the equipment.

Danger

The four indicator LEDs flash slowly.

MAX

/

MIN

alarm

System Malfunction 1

LEDs flash slowly

Fault:

The max. admissible temperature in the electrode terminal box is exceeded.

Remedy: Insulate electrode flange to protect the equipment against heat radiation.

The four LEDs flash rapidly.

MAX

/

MIN

alarm

System Malfunction 2

LEDs flash rapidly

As soon as the temperature drops below the max. admissible limit the equipment
automatically returns to normal operation.

Fault:

The CAN bus line between the nodes is interrupted.

Remedy: Check wiring and terminals. Restart system.

Fault:

Incorrect node ID settings.

Remedy: Set correct node ID(s), referring to sections “Basic Adjustment” and “Annex”.

Disconnect the system from its power supply. After 5 sec. connect
power and restart system.