Notes regarding grid connection

Monitoring the
Grid

AC terminals

PE

Ground conductor / grounding

L1

Phase conductor

N

Neutral conductor

Max. cross-section of each conductor cab-
le:
16 mm²

Min. cross-section of each conductor cable:
in accordance with the fuse rating on the
AC side, but at least 2.5 mm²

The AC cables can be connected to the AC
terminals without ferrules.

In the case of an AC cable with a cross-section of 16 mm², ferrules can be either not used
or only used to a limited extent depending on the type of ferrule and crimping.

Type of AC cable

The following types of AC cable can be connected to the AC terminals of the inverter:

IMPORTANT! The resistance in the leads to the AC-side connection terminals must be as
low as possible for optimal functioning of grid monitoring.

min. 2,5 mm² - max. 16 mm²
min. 1,5 Nm - max. 1,8 Nm

-

copper or aluminium: round, single wire

-

Copper: round, finely stranded up to conductor category 4

Cu / Al Cu

max. Class 4