FIREPLACE INSTALLATION

Continued

FIREPLACE INSTALLATION

Checking Gas Connections (Cont.)

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Figure 33).

2.

Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas fireplace or opening main
gas valve located on or near gas meter for natural gas fire-
place, or using compressed air.

3.

Check all joints from propane/LP supply tank or gas meter to
equipment shutoff valve (see Figure 34 for propane/LP or Figure
35 for natural gas). Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak. Correct all leaks at once.

Figure 33 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane/LP
Supply Tank

Gas Valve

Equipment
Shutoff
Valve

Gas
Meter

Gas Valve

Equipment
Shutoff
Valve

Pressure Testing Fireplace Gas Connections

1.

Open equipment shutoff valve (see Figure 33).

2.

Open propane/LP supply tank valve for propane/LP fireplace
or main gas valve located on or near gas meter for natural gas
fireplace.

3.

Make sure control knob of fireplace is in the OFF position.

4.

Check all joints from equipment shutoff valve to gas valve
(see Figure 34 for propane/LP or Figure 35 for natural gas).
Apply noncorrosive leak detection fluid to all joints. Bubbles
forming show a leak. Correct all leaks at once.

5.

Light fireplace (see Operating Fireplace, pages 26 through
28). Check all other internal joints for leaks.

6.

Turn off fireplace (see To Turn Off Gas to Appliance, page 26).