Specifications, Overview, Environmental – Geist XP Series User Manual

Page 3: Electrical, Receptacle ratings

Advertising
background image

GM1098 Rev 2

3

Rev Date: 7/29/2014

Specifications


Overview

The XP Series products are Power Distribution Units (PDU) intended for connection to a 30 Amp
AC Mains circuit

1

. The PDUs are designed to be powered by either a single phase or a three phase

AC input circuit. Three phase units can be configured for either a delta or wye input connection.
XP Series PDUs can optionally be configured with a Geist Current Meter that provides local
monitoring and display of each output circuit current. Alternatively, XP Series PDUs can be
configured with a Geist Current Monitoring (EM) Meter that provides both local and remote
monitoring of input and output line current. XP Series PDUs can also be configured with advanced
wireless technology from Packet Power which allows for remote monitoring of input and output
power through a wirelessly connected gateway.

Environmental

Temperature

Operating:

10°C (50°F) min

45°C (113°F) max

Storage:

-25°C (-13°F) min 65°C (149°F) max

Humidity

Operating:

5% min

95% max

(non-condensing)

Storage:

5% min

95% max

(non-condensing)

Elevation

Operating:

0 m (0 ft) min

2000 m (6561 ft) max

Storage:

0 m (0 ft) min

15240 m (50000 ft) max

Electrical

See nameplate for unit ratings.

Receptacle Ratings

NEMA 5-15R or L5-15R

125 Volts, 15 Amp

NEMA 5-20R or L5-20R

125 Volts, 20 Amp

NEMA 6-20R or L6-20R

250 Volts, 20 Amp

IEC-320 C13

125/250 Volt, 15 Amp (per Receptacle Bank)

IEC-320 C19

125/250 Volt, 20 Amp

Networking (For Current Monitoring (EM) Meter Units Only)

Protocols

HTTP, ICMP, DHCP, TCP/IP, FTP

Ethernet Link Speed

1

Global Versions of the XP Series are intended to be connected to a 32 Amp AC Mains Branch

Circuit

Advertising
This manual is related to the following products: