Groth 7758A User Manual

Page 2

Advertising
background image

Table of Contents

Section

Page

Introduction

2

Specifications

1

Design & Function

3

Installation

3

Maintenance

4

Model Identification

7

Product Limited Warranty

7

Tables

Bolt torque

4 & 5

MESG tables

6

Attachments

Drawing A-93536

Test reports [as required]

INTRODUCTION

This manual is intended to provide recommended
procedures and practices for installation, operation
and maintenance of the Groth Model 7758A stable
detonation flame arrester without restriction. Any
standard procedures and practices developed for a
specific plant or process should supersede this
manual. Although this manual cannot cover all
possible contingencies, following these guidelines
will provide safe, reliable detonation flame arrester
service.

The arrester shall be treated as a safety device and
must be maintained by a knowledgeable repair
technician. Carefully read and understand this
Manual before installing or servicing this product.
Groth Corporation offers repair services for all
products manufactured by the Tank Protection
Division.

For information not contained in this manual, please
contact:

Groth Corporation

A Continental Disc Company

13650 North Promenade Blvd.

Stafford, TX 77477

Phone 281-295-6800

Fax 281-295-6999

CERTIFICATION

Groth Model 7758A stable detonation flame
arresters are manufactured in compliance with the
ATEX Directive 94/4/EC, as confirmed by
Certificate

IBExUXXXXX X

. This certification covers

the following sizes, materials and limits for use.

Sizes included are all those shown on drawing A-
93536. Materials included are all materials that
satisfy the strength and pressure ratings specified
on these drawings.

These arresters are suitable for in line unstable
detonations and short time burning.

*

Each temperature sensor with respect to connection size has

a trigger emergency function within half of the burn time.

Must be installed with integrated temperature
sensor(s), Groth P/N 93219005 or equal.

INTEGRATED TEMPERATURE SENSORS

Detonation flame arresters for short time
burning must be fitted with one or more
integrated temperature sensors, taking into
account the intended orientation of the flame
arrester. These arresters may be used in
systems and situations where the flow of the
flammable mixture can be stopped within one
minute.

Explosion Gas

Group

IIB3

MESG of

vapor mixture

0.025" [0.65 mm]

Operating

Temperature

–4

o

F to 140

o

F [-20

o

C to 60

o

C]

Maximum Allowable

Burn Time

*Temperature Sensor
Emergency Function

Connection

Size

Burn

Time

Trigger Time

8”-12"

30

Minute

s

15 Minutes

(200 -305 mm)

IOM-7758A

Ref. ID 97895

2