Groth 8860 User Manual

Page 8

Advertising
background image

IOM -8860

Page 8 of 13

13650 N. Promenade Blvd. * Stafford, TX 77477

Office: (281) – 295-6800 * (800) – 354-7684 * Fax: (281) – 295-6999 * www.grothcorp.com


TABLE 3

SPRING TABLE: MODEL 8860

Flange

Min. Setting

Max. Setting

Spring P/N

Scale P/N

Size

2”

2” WC

12” WC

SPR8860020120

313000101

2”

8” WC

24” WC

SPR8860020220

313000201

3” & 4”

2” WC

12” WC

SPR8860030120

313000101

3” & 4”

8” WC

24” WC

SPR8860030220

313000201

6” & 8”

2” WC

12” WC

SPR8860060120

313000101

6” & 8”

8” WC

24” WC

SPR8860060220

313000201

10” & 12”

2" WC

6” WC

SPR8860100320

313000301

10”

5” WC

12” WC

SPR8860100520

313000401

10” & 12”

10” WC

22” WC

SPR8860100420

313000501

10” & 12”

20" WC

44” WC

SPR8860100620

313000601

12"

3” WC

8” WC

SPR8860100520

313000701

12"

5” WC

12” WC

SPR8860120520

313000401


VI. TROUBLESHOOTING

GUIDE

PROBLEM

INSPECTION

SUGGESTED CORRECTIVE ACTION

Vapor flowing at line
pressure below specified
set point.

Flow indicator or vapor
discharge.

Damaged seat/disc or setting too low.

If original pressure setting has not been disturbed, remove
regulator and repair.

Vapor not flowing at line
pressure above specified
set point.

Flow indicator or vapor
discharge.

Damaged diaphragm or pressure setting too high.

If original pressure setting has not been disturbed, remove
regulator and repair.

Inspect the bushings for debris or damage.

Gas leaking from upper
vent.

Emission indication
near the regulator.

Damaged diaphragm.

Remove regulator and replace diaphragm.

System pressure above
specified operating
range.

Observe pressure
indicator during
operation.

Damaged diaphragm or pressure setting too high.

Vapor flow exceeds capacity of regulator.

System pressure below
specified operating
range.

Observe pressure
indicator during
operation.

Damaged seat/disc or setting too low.

Insufficient vapor production.

VII. PREVENTATIVE MAINTANANCE


Periodically, while in service, examine the regulator for leakage at bolted connections, adjusting
screws, and vent. Test for process vapor emissions from vent caps.

Periodically, out of service, examine seat and pallet for a smooth surface to ensure proper seating and
sealing. Examine actuator diaphragm for cuts, or unusual wear.

VIII. RECOMMENDED SPARE PARTS

 Spring; see Table 3 for correct part number

 Vent part number 285320147 (1/4” NPT)

 Soft Goods Kit; see Table 4 for correct part

numbers

Table 4: Soft Goods Kits

Size Buna-N EPDM

FKM

2”-4” KS886002B

KS886002E

KS886002V

6”-8” KS886002B

KS886002E

KS886002V

10”-12”

KS886002B

KS886002E KS886002V