Herrmersion RE

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

5

www.herrmidifier-hvac.com

WARNING

Never service any component without first disconnecting all

electrical supplies to the unit or severe personal injury or

death could occur.

CAUTION

Insure that all power sources conform to the unit requirements

or damage to the unit may result.
These units have been designed for any tap, softened, de-

ionized (DI) or reverse osmosis (RO) water applications.

With tap/softened water, an adjustable drain cycle and

skimmer cycle are provided to automatically drain away

some water contaminants; reducing cleaning intervals. For

DI/RO water, the system is virtually maintenance free. The

skimming cycle may be deactivated via the keypad.

Follow installation instructions CAREFULLY to avoid creating

unsafe conditions. All electrical wiring should be done and

checked by a qualified electrician using copper conductors

only. All piping connections should be made and leak-tested

by a qualified service technician, per instructions in this

manual.

Make certain that the power source conforms with to the

electrical requirements of the unit. Disconnect power before

installing or servicing the unit. If power disconnect is out of

visual sight, lock it into open position and tag it to prevent

unexpected application of power. Failure to do so could

result in fatal electrical shock.

WARNING

Do not depend upon a unit control switch or other switch as

the sole means of disconnecting power when installing or

servicing the unit. Always disconnect power at main circuit

breaker. Failure to do so could result in fatal electrical shock.
Special attention should be given to grounding this unit. To

prevent the risk of electrocution, the unit must be securely

and adequately grounded. This should be accomplished by

connecting a grounded conductor from the service panel to

the grounding lug located inside the control section of the

unit. To ensure proper ground, a qualified field technician

must test the grounding means.

Do not defeat safety interlocks, such as the high temperature

limit or door switch. Do not attempt to operate the unit without

the doors installed.

In cases in which property damage may result from

malfunction of this unit, a backup system should be used.

WARNING

Do not place unit in a location where service personnel can

not safely service this equipment or personal injury could

occur.

INSTALLATION

WARNING

Open all disconnect switches and secure in that position

before installing unit. Failure to do so may result in personal

injury or death from electrical shock.

UNIT LOCATION & MOUNTING

The Herrmersion – RE unit is designed to be mounted on a

wall and should be located as close to the dispersion means

as possible (i.e. close to the duct being served with the

steam). This will minimize energy losses.

The unit requires electrical and plumbing connections and

should be mounted in such a way to facilitate access to these

connections.

In order for the magnetic water level switches and the

skimmer function to operate properly, the unit must be

mounted level and plumb with reference to the front and top

of the unit.

The cabinet is designed to safely dissipate heat to protect

the electronics. Herrmersion – RE humidifiers, steam piping

and any other accessories should be located in a manner to

facilitate routine inspection and any necessary maintenance.

The unit should not be located above (false ceilings) or

around valuable property where a malfunction could cause

damage. Minimum clearance around the cabinet must be

maintained.

Minimum Access Requirements

Left

2”

Right

24”

Top

12”

Bottom

10”

Front

36”

Minimum access is 36” to the front for periodic removal of the

steam tank for service and 24” to the right side for access to

the electrical components.

Four lag bolts (2) 5/16” and (2) ¼” are supplied for securing

the unit to the wall. Install the top two lag bolts (5/16”)

according to the dimensions shown below. Hang the unit

on the wall, and then install the bottom two lag bolts (1/4”).

Finally, secure all four lag bolts. Be sure the unit is level and

mounted directly to a wall constructed of wood studs at least

2” thick (or equivalent).

Mounting location must be capable of supporting the entire

weight of the unit. Please refer to the previous table for

operating weight of the unit.