Herrmersion RE

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

7

www.herrmidifier-hvac.com

Standard Duct Distribution

STEAM DISCHARGE MUST ALWAYS

BE FROM THE TOP OF DISTRIBUTOR

VERTICAL DUCT

HORIZONTAL DUCT

NO SAGS

ALLOWED

MIN. 8% (1" PER FOOT)

10" MIN.

(254mm)

The rubber vapor hose carries the steam to the dispersion

tube and condensate back to the unit tank. It must have an

8% (1” per foot) pitch back to the unit. Support the vapor

hose so that it maintains proper pitch when the unit is in

operation.

Single Distribution Tube

DUCT HEIGHT

10" - 16"

(254MM) - (406MM)

DUCT HEIGHT > 16"

(406mm)

(76mm)

h =

H

2

-5" (127mm)

h

3"

H

Units up to 45 pounds per hour of steam will use one steam

distribution tube. Refer to the diagram above for mounting

location.

Dual Distribution Tubes

h (in)=6+

(H-15)

2

(76mm)

DUCT HEIGHT > 16"

(406mm)

AIR

FLOW

DUCT HEIGHT

10" - 16"

(254MM) - (406MM)

3.00" (76mm)

6.5" (165mm)

8.00

(203mm)

3"

h

H

Units above 45 pounds per hour of steam will use two duct

dispersion tubes. Refer to the diagram above for mounting

location.

Single to Dual Duct Distribution

EST-255

"Y" CONNECTOR

If you must split the discharge of one steam outlet into two

ducts with the same static pressure, a “Y” connector is

available from the factory. The length of vapor hose after

the “Y” connector must be the same to ensure equal steam

distribution.