Propane/lp gas heater cgp10a and cgp6, Connecting to gas supply – Desa CGP10A User Manual

Page 8

Advertising
background image

8

101871

PROPANE/LP GAS HEATER

CGP10A AND CGP6

IMPORTANT:

Hold pressure regulator with wrench when connecting it to gas piping and/

or fittings.

Figure 13 - Gas Connection

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test
Gauge
Connection *

Tee
Joint

Pipe
Nipple

Cap

Pressure
Regulator

Heater
Cabinet

3/8" NPT
Pipe Nipple

Ground Joint Union

Sediment Trap

* An A.G.A. design certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design certified manual
shutoff valve from your dealer. See Accessory, page 15.

Manual
Shutoff
Valve *

From
External
Regulator
(11" W.C. to
14" W.C.
Pressure)

3" Minimum

CONNECTING TO
GAS SUPPLY

NOTICE: A qualified service per-
son must connect heater to gas
supply. Follow all local codes.

The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
12. Pointing the vent down protects it from
freezing rain or sleet.

Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

Installation must include a manual shutoff
valve, ground joint union, and plugged 1/8"
NPT tap. Locate NPT tap within reach for
test gauge hook up. NPT tap must be up-
stream from heater (see Figure 13).

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

Propane/LP
Supply
Tank

Figure 12 - External Regulator With Vent
Pointing Down

CAUTION: Never connect

heater directly to the propane/LP
supply. This heater requires an
external regulator (not supplied).
Install the external regulator be-
tween the heater and propane/LP
supply.

CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Vent
Pointing
Down

External
Regulator

Advertising