INSTALLATION PRECAUTIONS

1.

The Battery Saver Low Ripple is AC Input AND DC Output over-current protected
as follows:
>

120VAC 60Hz Input Fuse: 5 Amp

>

DC Output: ATC, 15 Amp

Note: The external ATC 15 Amp DC OUTPUT FUSE is common to both the
Battery Saver output AND the vehicle battery connection that supplies power to the
load when the Battery Saver is OFF (120VAC to Battery Saver - OFF).

2.

OVERLOADING the Battery Saver in excess of 15 amperes when the BSLR
is ON:
A.

In excess of 20 amperes: initiate current limiting of the Battery Saver
output with a corresponding reduction in output voltage.

B.

In excess of 20 amperes: causes the ATC 15 Amp DC OUTPUT
FUSE to open within 2 minutes.

3.

OVERLOADING the Battery Saver in excess of 20 amperes when the BSLR
is OFF:
A.

When the BSLR is OFF, loads are powered by the battery, which is
overload protected with a ATC 15 Amp fuse. The fuse will open
when the current exceeds 20 amperes for 2 minutes

Manage Battery Saver Connected Loads to 10 Amperes or
Less!