Legrand 8801S-FC Series User Manual

Page 4

Advertising
background image

4

1, 1 1/2, 2

8801S-FC

2" [51mm]

5 1/4" [133mm]

1, 1 1/2, 2

8802S-FC

2" [51mm]

5 1/4" [133mm]

1, 1 1/2, 2

8803S-FC

2" [51mm]

5 1/4" [133mm]

1, 1 1/2, 2, 3

8801S-FC2

2" [51mm]

6 1/2" [165mm]

1, 1 1/2, 2, 3

8802S-FC12 2" [51mm]

6 1/2" [165mm]

1, 1 1/2, 2, 3

8803S-FC12 2" [51mm]

6 1/2" [165mm]

pour Height
Hauteur de

chape
altura de

volcado

ClaSSiFiCation

Catalog

minimum

maximum

rating

numBer

Pour HeigHt

Pour HeigHt

Floor Box HeigHt adjuStment rangeS
PlageS de réglage de la Hauteur deS BoîteS de Sol
rangoS de ajuSte Para la altura de laS CajaS Para PiSoS

minimum tHiCkneSS For Fire reSiStanCe rating

Cement tyPe

1 Hour

1 1/2 Hours

2 Hours

3 Hours

Normal Weight 3 1/2" [89mm] 4 5/16" [109mm]

5" [127mm]

6 3/16" [158mm]

Lightweight

2 1/2" [64mm]

3 1/8" [79mm] 3 5/8" [91mm]

4 7/16" [112mm]

reinForCed ConCrete SlaB (plywood Decking)

minimum tHiCkneSS For Fire reSiStanCe rating

Cement tyPe

1 Hour

1 1/2 Hours

2 Hours

3 Hours

Normal Weight 3 1/2" [89mm]

4" [102mm]

4 1/2" [114mm]

5 1/5" [133mm]

Lightweight

2 5/8" [67mm]

3" [76mm]

3 1/4" [83mm]

4 3/16" [106mm]

Corrugated deCking

Fire ClaSSiFiCation rangeS & minimum tHiCkneSS

tab

languette

Pestaña

a. remove screw
retirez la vis
Quitar tornillo

B. Slide out tab
Faites glisser la languette
deslizar la pestaña

C. remove tab

Dépose de la languette
Quitar pestaña

tab rEmoVaL (4 tabs):
rEtraIt DE La LaNgUEttE (4 languettes) :
QUItar pEStañaS (4 pestañas):

tab

languette

Pestaña

Advertising