Installation instructions – Legrand DSBEA User Manual

Page 6

Advertising
background image

Legrand Delta Strut Solar Systems

have passed electrical/bonding

testing per UL 2703. The following

paragraph states the scope of the

UL standards:

These requirements cover rack

mounting systems and clamping devices

for flat-plate photovoltaic modules and

panels that comply with the standard

for Flat-Plate Photovoltaic Modules

and Panels, UL 1703, intended for

installation on or integral with buildings,

or to be freestanding (i.e., not attached

to buildings), in accordance with the

National Electrical Code, ANSI/NFPA 70

and Model Building Codes.

Installation Instructions:

1. Snap chalk lines for each

Universal Solar Support (USS)

row. Rows should be located at

even intervals with a maximum

distance of 60”. Actual spans

should be based upon roof

loading requirements.

2. Snap a second set of chalk

lines at a right angle to

correctly position the Delta

Strut stringers. Actual spacing

will vary based upon PV

panes size, angle and shading

requirements.

3. Place USS according to

chalk lines.

4. Load USS with concrete ballast

blocks in each of the three

cavities. Additional ballast can

be added to each USS base by

stacking ballast blocks on both

sides of the base. This should

be done within the loading

requirements of the roof and the

wind requirements of the array.

[Figure A]

5. Install Delta Strut stringers to

angle supports. Position Delta

Strut using the built-in position

tabs, then secure with a DSPCC

Connection Clamp and self-

threading screw. [Figures B, C]

6. Splice sections of Delta Strut

together using a DSSA splice

kit. Use both splices in the kit

for a single splice. Torque nuts

to 6-8 ft/lbs. [Figure D]

7. If you are using an Adjustable

Universal Solar Support (USSA),

you can adjust the support

height to make allowances for

low areas in the roof.

8. Attach cable bracing onto rear

and front of USS supports using

Cable Bracing Kit.

9. Place feeder cables into Delta

Strut stringer row(s).

10. Position first PV panel at the

beginning of first run, check for

position and square, then attach

to Delta Strut using DSEHDC

End Bolt/Clamp. Torque nuts to

6-8 ft/lbs.

11. Add next PV panel in run. Use

DSMHDC (Middle Bolt/Clamp -

Patent Pending) in areas where

two panels adjoin. Torque nuts

to 6-8 ft/lbs. [Figure E]

12. Connect PV cables and secure

cabling to Delta Strut. Be aware

that cabling is live at this point.

13. Each solar row to be connected

to Earth as specified in NEC

using proper sized ground

conductor and UL Listed Split-

bolt lug connected to Delta

Strut. [Figure F]

Roof mounted solar panels supported by

Delta Strut and USS Angle Support

DSMHDC is spring-loaded and

stays in position while panels

are positioned.

DSMHDC

Load Universal Solar Support

(USS) with standard 4” x

8” x 16” concrete blocks.

Ballast blocks can be

stacked for greater wind load

requirements.

Use punched pilot hole in USS

to allow connection clamp

clearance from cross wire.

DSPCC

Position Delta Strut stringers

using built in positioning tabs

on USS.

Use two DSSA to splice any two

sections of Delta Strut tray.

DSSA

Use GNDSB split-bolt lug

grounding connector to

properly ground each solar

support row.

GNDSB

FIGURE A

FIGURE B

FIGURE C

FIGURE D

FIGURE E

FIGURE F

B/C

E

A

Advertising
This manual is related to the following products: