Sensor adjustment & programming – Legrand RW3U600 User Manual

Page 4

Advertising
background image

Call 800.223.4185 for Technical Support

SENSOR ADjUSTMENT & PROGRAMMING

To program the RW3U600, you use controls

located under the ON/OFF button. The wall

switch cover plate must be removed to gain

access to the mode button and adjustment

trimpots under the ON/OFF button.

For multi-way operation, the

Operating Mode and the Time Delay

adjustments should be the same in all

sensors related to the same load.

1. Firmly grasp the side edges of the

Lock Bar and gently pull it away from

the switch face until it clicks. Do NOT

attempt to pull the Lock Bar off of the

switch!

2. Firmly grasp the side edges of the ON/

OFF button. Slide the button downward

approximately 1/2 inch to expose

the mode button and adjustment

trimpots.

Setting up the Operating Mode

Select the operating mode by pressing the Mode button. The green LED behind

the switch button blinks to indicate the selected mode:
• One blink indicates Mode 1 (Vacancy Sensor Operation), Manual-ON/OFF,

Auto-OFF.

• Two blinks indicates Mode 2 (Occupancy Sensor Operation), Auto-ON/OFF with

manual control and reset to auto (after 5 minutes of vacancy).

To change the operating mode, press the Mode button. The LED blinks to indicate

the selected mode. After that, the unit operates in the indicated mode.

Adjusting the Time Delay

Turn the right trimpot counter-clockwise to reduce the amount of time the lights

will remain on after the last motion detection (minimum = 15 seconds). Turn the

same trimpot clockwise to increase this time delay (maximum = 30 minutes).

You can only select the following values: 15 seconds/5 minutes/15 minutes/

30 minutes.

Warning: Do not overturn the Time Delay adjustment trimpot!

Adjusting the Light Level

This feature is factory set at maximum, so that even the brightest light will not

prevent the sensor from turning the load ON when it detects occupancy. If this

feature is not needed, leave the light level at maximum, fully clockwise.
The light level must be adjusted when lights would normally be turned OFF

because there is enough natural illumination. Each RW3U600 may have a

different light level setting.
1. Set all RW3U600s to Mode 1 (Manual-ON) - except for the one that you’re

adjusting.

Set the RW3U600 you’re adjusting so that it is in Mode 2 (Automatic-ON).
2. Reduce the time delay to 15 seconds.
3. Adjust the Light Level trimpot to minimum (fully counter-clockwise) on the unit

that you’re adjusting. Move out of the coverage area. Let the sensor time out so

lights are OFF and then wait 30 seconds more.

4. Without casting a shadow on the sensor, enter the area. The lights should

remain OFF. Adjust the Light Level trimpot clockwise in small increments.

After each adjustment, wait 5-10 seconds to see if the lights turn ON.

Continue this procedure until the lights turn ON. At this setting the light will

not turn ON automatically with occupancy the if light level measured at this

sensor is above the current natural illumination.

5. Repeat the process (beginning with step 1) for each RW3U600 in your multi-

way configuration until the Light Level has been adjusted properly in all of

them.

6. When you have finished adjusting the Light Level of all the RW3U600s, return

them all to Mode 2.

7. Reset the time delay to the desired setting in all units.

Warning: Do not overturn the Light Level adjustment trimpot!

723

,1'22586(21/<

Fig. 6: Sensor Adjustment Controls

Advertising
This manual is related to the following products: