4) Connecting Rack Power

a) Derating of 96 Channel Systems
Rack systems containing 96 circuits of 20 amp dimmers MUST be derated to a lower
total load capacity. The total allowed load for these systems is 218,880 watts. This is
95% of the theoretical capacity of 230,400 watts if the system were not derated.

b) Ampacity and Conductor sizing
This chart shows the proper conductor size to allow 20 amp Leprecon Dimming System
to be used to it’s full load capacity. Note that systems above 48 channels MUST be
wired with three phase service. Wire sizes are based on NEC 310. Further derating may
be necessary based on conditions and local codes.

Note: Conductors must be rated for 90 degrees Celsius.

For fully loaded 20 amp systems. Wire size based on 4 conductors in conduit.

# of

Channels

Single Phase

Current Rating

(A) per leg

Min Wire

Size

# of

conductors

per terminal

Three Phase

Current

Rating (A)

per leg

Min Wire

Size

phase and

neutral

# of

conductors

per terminal

12

120

1/0

1

80

3 awg

1

24

240

1/0

2

160

1/0

2

36

360

4/0

2

240

1/0

2

48

480

350 MCM

2

320

3/0

2

60

N/A

400

250 MCM

2

72

N/A

480

350 MCM

2

84

N/A

560

500 MCM

2

96

N/A

608*

500 MCM*

2

For fully loaded 10 amp systems. Wire size based on 4 conductors in conduit.

# of

Channels

Single Phase

Current Rating

(A) per leg

Min Wire

Size

# of

conductors

per terminal

Three Phase

Current

Rating (A)

per leg

Min Wire

Size

phase and

neutral

# of

conductors

per terminal

12

60

4 awg

1

40

6 awg

1

24

120

1/0

1

80

3 ga

1

36

180

1/0

2

120

1/0

1

48

240

1/0

2

160

3/0

1

60

300

3/0

2

200

1/0

2

72

360

4/0

2

240

1/0

2

84

420

300 MCM

2

280

2/0

2

96

480

400 MCM

2

320

3/0

2