Dip switch features (es142-m2 and es142-m2-s only), Dip switch features – Dodge ES142 User Manual

Page 6

Advertising
background image


Dodge Engineering & Controls, Inc.

Toll Free (877) 334-2875 Fax: (978) 244-1422

Installation

ES142 Spring Return Electronic Actuators

129-270 EAI/ES-6 DEI,

Inc.

DIP Switch Features

(ES142-M2 and ES142-M2-S Only)

Counterclockwise

Self-adapt feature

2 to 10 Vdc

Tandem Mount

Master

Clockwise

Self-Adapt Off

0 to 10 Vdc

Single Mount

Slave

Figure 11. DIP Switch Settings.

• After setting the 4th DIP switch for TM (tandem mount) on all actuators used in the

tandem application, one actuator must be identified as the Master by selecting the
"M" on the 5th DIP switch.

• The rest of the actuators used in the application should have the "S" (slave) set on

the 5th DIP switch.

• Connect all the 2 (black) Neutral wires and connect them to the power supply.
• Connect all the 1 (red) Supply wires and connect them to the power supply.
• The Output Signal 9 (pink) wire identified as the Master actuator, needs to be

connected to all the Control Signal Wires 8 (gray) of the slave actuators used in the
tandem application.

Operating

Voltage

Power

Consumption

Modulating Control

24 Vac/dc

9 VA/7W

2-Position and 3-Position Control

24 Vac/dc

8 VA/6W

120 Vac

9 VA

Advertising