Monster HTUPS 3700 User Manual
Page 42

34
For example:
ON3 <cr> : UPS turn on the bank-3 outlets .
note:
a . Master/Slave slide switch is enabled:
The bank-0 outlet is master outlet . The slave outlets ( bank-1 and bank-2 ) turn on or off, they will depend on the
master outlet output power . If the master outlet output power is over 45W, the slave outlets will be turned on . If the
master outlet output less than 25W, the slave outlets will be turned off .
The master outlet will be turned on after 8 seconds when UPS is plugged into utility power .
UPS will not accept the “ON0<cr>”,”ON1<cr>”,“ON 2<cr>” and “R<cr>” commands . The monitor software will
not send these commands to UPS .
The “ON6<cr>” command only control the bank-3/4/5 outlets .
b . Master/Slave slide switch is disabled:
The bank-0, bank-1 and bank-2 outlets are defined to unswitched outlets . The unswitched outlets will be turned on
after 8 seconds when UPS is plugged into utility power . Or the monitor software send the “ON0<cr>”, “ON1<cr>”
and “ON2<cr>”, “ON3<cr>”, “ON4<cr>”, “ON5<cr>” to turn on the bank-0, bank-1, bank-2, bank-3, bank-4
and bank-5 outlets .
The “ON6<cr>” command can turn on all the outlets ( bank-0/1/2/3/4/5 ) .
RS-232 COMMUnICaTIOnS PROTOCOl anD COMManD SeT
COn’T