Monster HTUPS 3700 User Manual
Page 44

36
For example:
OF3<cr> : UPS will turn off the bank-3 outlets .
note:
a . Master/Slave slide switch is enabled:
The bank-0 outlet is master outlet . The slave outlets ( bank-1 and bank-2 ) turn on or off, they will depend on
the master outlet output power . If the master outlet output power over 45W, the slave outlets will be turned
on . If the master outlet output less than 25W, the slave outlets will be turned off .
The master outlet will be turned on after 8 seconds when UPS is plugged into utility power .
UPS will not accept the “OF0<cr>””OF1<cr>” and “OF 2<cr>” commands . The monitor software will not
send these commands to UPS .
The “OF6<cr>” command only control the bank-3/4/5 outlets .
b . Master/Slave slide switch is disabled:
The bank-0, bank-1 and bank-2 outlets are defined to unswitched outlets . The unswitched outlets will
be turned on after 8 seconds when UPS is plugged into utility power . The monitor software can send the
“OF0<cr>”, “OF1<cr>”, “OF2<cr>”, “OF3<cr>”, “OF4<cr>”and “OF5<cr>” to turn off the bank-0,
bank-1, bank-2, bank-3, bank-4 and bank-5 outlets .
The “OF6<cr>” command can turn off all the outlets ( bank-0/1/2/3/4/5 ) .
RS-232 COMMUnICaTIOnS PROTOCOl anD COMManD SeT
COn’T