Installation – Montigo L38DF-ST User Manual

Page 15

Advertising
background image

L38DF-ST* Indoor Gas Fireplace

Page 15

XG0810 - 150204.2

Installation

42”

42”

26 3/4”

12”

Figure 13b. Side Vented, wall mounted Multi-elbow termination

installation. Installation for L38DF*-ST must have a minimum

vertical rise of 42".The vent run must comply with the Venting

Graph for Rear vent, wall mounted terminations, Figure 13.

Figure 13a. Straight run, Side Vented, wall mounted termination for

L38DF-ST*, Figure 13.

Notes Wall Mounted Terminations: SIDE VENT

„

All dimension lengths for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graphs,

see Figure 13.

„

Fireplace must be converted to Rear Vent configuration prior to

running vent, see Figure 8 and 8a.

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 120" and the horizontal

run to the wall flange of the vent termination is 138", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 48" and the horizontal

run to the wall flange of the vent termination is 96", this would be

would NOT be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and

the horizontal run to the wall flange of the vent termination is 120",
this would NOT be an acceptable installation.

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

30” Max.

42” Min.

12”

Max.

Flex or Rigid

Section

15 1/4”

Min.

26 3/4”

Hearth

26 3/4”

PXT Extension

RHS101 Heat

Shield

Termination

Hearth

Exterior

Wall

NOTE:

12” MAX. horizontal

run with no vertical lift.

12” MAX.

If your installation does not fall within

the venting parameters, contact a

local Montigo dealer for Power

Venting options.

A

C

B

Figure 13. Side Vent Venting Graph for wall mounted terminations.

Note: Images are shown without screens for clarity purposes. How-

ever, your fireplace should not be operated without proper installation

of screens.