L38DF-ST* Indoor Gas Fireplace

Page 8

XG0810 - 150204.2

Installation

When installing a shelf over the top of the fireplace, the following

guidelines must be adhered to:

For Side Vent applications, the minimum clearance is 10" from the

top of the fireplace to the underside of any combustible shelf.

For Top Vent applications, the minimum clearance is 17½" from the

top of the fireplace to the underside of any combustible shelf.

MODEL

Top - T

op vent

Top - Side vent

Sides

Floor

Mantel

L38DF-ST*

17½"

10"

1"

0"

See

Section 6

Finishing

around the

fireplace

NOTE: Clearance from top of fireplace to a ceiling within the fire-

place enclosure.

Clearances

1” clearance is maintained on sides and bottom of vent runs and 2”

above horizontal vent runs to any combustible material.

Installing the Nailing Flange Extension

Once the fireplace is placed into the rough framed opening, the

supplied Nailing Flange Extension (Part No. H38074) must be fasten

securely into place, with nails or wood screws. as shown in Figure 7.

Installing the supplied non combustible header
Included with the L38DF-ST* gas fireplace are two metal headers

made of galvanized steel. The metal headers must be installed after

the fireplace has been back framed in place. Install metal headers at

34 1/2" from the base of the unit, as shown in figure 6.

40”

34 1/2”

Figure 6. Installing the supplied metal headers, both sides typical.

Figure 7. Installing the Nailing Flange Extension.
Note: The nailing flange extension can be substituted with a piece

of NON-Combustible material of the same size and thermal char-

acteristics, ie: cement board or equivalent. This is recommended in

applications where the facing materials will not adhere to the metal

nailing flange.

6"

Supplied

Non-Combustible

Header