Appendix A - Termination Locations

A = clearance to the termination frame above grade, veranda, porch, deck,

or balcony [16 inches (41 cm) minimum]

B = clearance to door, or sides and top of window, that may be opened [16

inches (41 cm) minimum for appliances ≤100 000 BTU/H (30kW)]

C = clearance to bottom of window that may be opened horizontally [36

inches (92 cm) minimum for appliances ≤100 000 BTU/H (30kW)]

D = no clearance to permanently closed window when installed with ap-

proved glass penetration termination

E = clearance to permanently closed window [16 inches 41 cm recom-

mended to prevent condensation on window]

F = vertical clearance to ventilated soffit located above the termination

within a horizontal distance of 2 feet (61 cm) from the centreline of the

termination [22 inches (56 cm) minimum]

G = clearance to unventilated soffit

[16inches (41 cm) minimum to non-combustibles]

[22 inches (56 cm) minimum to combustibles]

H = clearance to outside corner [9 inches (23 cm) minimum]
I = clearance to inside corner [12 inches (31 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator

K = clearance to service regulator vent outlet [3 feet minimum in the United

States] [*6 feet (1.8 m) minimum in Canada]

L = clearance to nonmechanical air supply inlet to building or the combus-

tion air inlet to any other appliance [16 inches (41 cm) minimum for

appliances ≤100 000 BTU/H (30kW)]

M = clearance to mechanical air supply inlet

[*6 feet (1.8 m) minimum]

N =

†

clearance above paved sidewalk or a paved driveway located on

public property [*7 feet (2.1 m) minimum]

P = clearance under veranda, porch, deck, or balcony

[16 inches (41 cm) minimum

‡

to non-combustibles]

[22 inches (56 cm) minimum

‡

to combustibles]

Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighbouring buildings

[18 inches (46 cm) minimum]

S = clearance from corner in recessed location

[12 inches (31 cm) minimum]

T = maximum depth in recessed location

[48 inches (122 cm) minimum]

U = minimum width for back wall of recessed location

[24 inches (61 cm) minimum]

V = no horizontal clearance between the frames of two terminations that

are level.

W = horizontal clearance between the frames of two terminations that are

not level. [36 inches (92 cm) minimum]

†

a vent shall not terminate directly above a sidewalk or paved drive-

way which is located between two single family dwellings and serves

both dwellings

‡

only permitted if veranda, porch, deck, or balcony has an open side

that is equal to or greater than the depth of the enclosed area

* as specified in CGA B149 Installation Codes. Note: local Codes or

Regulations may require different clearances