Specifications, System concept, Block diagram – Niveo Professional NUPS20-3 User Manual

Page 4: Normal operation

Advertising
background image

SPECIFICATIONS

Capacity

VA

1000VA

1200VA

1500VA

2000VA

3000VA

Input

Voltage

100VAC, 110VAC, 120VAC, 220VAC, 230VAC or 240VAC ±25%

Frequency

50Hz or 60Hz ±5%

Output

Voltage (Batt.

Mode)

100VAC, 110VAC, 120VAC, 220VAC, 230VAC or 240VAC ±10%

Frequency

50Hz or 60Hz ±1Hz

Waveform

Modified sine wave

Transfer Time

Less than 6ms (typical)

Battery

Battery Type

12V/7AH*2Pcs

12V/7AH*4Pcs 12V/9AH*4Pcs

Recharge Time

5 hours to 90% of full capacity

Indicator

LCD

LCD indicator for line-on, battery back-up, AVR protection,

load and battery level, overload and UPS cut-off

Alarm

Battery Back-up

Sounding every 3 seconds

Battery Low

Sounding every 1 second

Overload

Continue beeping sound

Protection

Overload

Fuse & current limited

Short Circuit

Fuse & current limited & cut-off

Batt. Low Cut-off

No battery drain after cut-off

Physical

Dimension,

D*W*H

390*182*285

Environment

Operating

Temperature

32℉-104℉ at full load, 0~90% relative humidity (non-condensing)

Noise Level

Less than 40db (at 1 meter)

Interface

USB&RS-232

Communication port

Software

imate

- 10 -

SYSTEM CONCEPT

The purpose to present this chapter is to give you more precise conception
about how UPS works..

1. Block Diagram

AVR.

INV.

CHA.

N.F.

N.F.

INPUT

OUTPUT

Fig. 1 shows how UPS works.

2. Normal Operation

There are two main loops when AC Utility normal the AC output loop and the

battery charging loop. The AC output gets power from AC utility input and

pass through AVR to support power to load. In the same time, the AC utility

input is converted by AC/DC CHA and support charging power to charge

batteries.

AVR.

INV.

CHA.

N.F.

N.F.

INPUT

OUTPUT

Fig. 2 shows how the UPS works when AC Utility normal.