3.3.2 Input Signal Connections
Make connections on the mother board, located in the main unit, at terminal strips
T3, T4 and T5. Do not exceed 4.5 in-lb (0.5 Nm) of torque when tightening.
3.3.2.1 Input Signal Connections from Temperature Sensors
* Reference (Black)
* Reference (Black)
* Signal (Red)
* Signal (Red)
* Shield
Temperature Inputs
Supply temperature
Sensor
Return temperature
Sensor
L1 N
Not Used
!
CAUTION
Shield connections are required for proper operation. Failure to use shielded cable may result in
erratic operation.