TABLE A-1

ISO-CARE SPECIFICATIONS

SIZE

15, 30, 50, 75, 100, 125, 150, 175, 200, 225, 250, 300, 400, and 500 kVA

NOMINAL INPUT VOLTAGES

208 OR 480 +5%, -10% @ 2.5% Increments

OUTPUT VOLTAGE

208Y/120, or 480/277

FREQUENCY (Hz)

50 to 60 Hz +/- 5%

TRANSFORMER TYPE

3 Phase Computer Grade, Dual-Shielded, Isolation Transformer

NOISE ATTENUATION:
COMMON-MODE
NORMAL MODE

-120 dB

20 dB/Decade

LOAD POWER FACTOR

.3 Leading or Lagging to unity

AUDIBLE NOISE

<35 dB. Measured on Response Curve ”A”

EFFICIENCY

96.7 at Full Loads 98.5% at Light Loads

OVERALL INRUSH RATING

200% of full load for 30 minutes

1000% of full load for 1 cycle

OUTPUT IMPEDANCE

3 to 5%

OPERATING TEMPERATURE

32° F (0° C) to 104° F (40° C)

STORAGE TEMPERATURE F (C)

5° F (-15° C) to 122° F (50° C)

OPERATING HUMIDITY

5-95% Non-Condensing

TABLE A-2

NRT SPECIFICATIONS

SIZE

15, 30, 50, 75, 100, 125, and 150 kVA

NOMINAL INPUT VOLTAGES

208 OR 480 VAC

OUTPUT VOLTAGE

208Y/120, or 480/277 VAC

FREQUENCY (Hz)

60 Hz +/- 5%

TRANSFORMER TYPE

3 Phase Computer Grade, Multi-Shielded, Isolation Transformer

NOISE ATTENUATION:
COMMON-MODE
NORMAL MODE

-126 dB

-20 dB/Decade

LOAD POWER FACTOR

.3 Leading to .3 Lagging

AUDIBLE NOISE

<35 dB. Measured on Response Curve ”A”

EFFICIENCY

96% at Full Loads 98.5% at Light Loads

OVERALL INRUSH RATING

200% of full load for 30 min
100% of full load for 1 cycle

STORAGE TEMPERATURE F° (C°)

5° F (-15° C) to 122° F (50° C)

OPERATING TEMPERATURE

32° F (0° C) to 104° F (40° C)

OPERATING HUMIDITY

5-95% without Condensation