REFRIGERANT SYSTEM MODULE WIRING

VCC-X Controller Technical Guide

38

Refrigerant System Module for VFD

Compressors Wiring

The OE370-26-RSMV Refrigerant System Module for VFD
Compressors (RSMV) monitors and controls one refrigeration circuit
of the HVAC unit. The module is designed for R410-A refrigerant.

The RSMV is connected to the VCC-X Controller (Orion Part No.
OE338-26B-VCCX; AAON Part No. V42430). Up to 4 RSMV’s
can be connected, depending on the size of the system. There are
2 E-BUS Expansion Ports which allow the use of communicating
sensors and the E-BUS Modules.

The RSMV provides 4 analog inputs, 3 binary inputs, 3 relays, and
4 analog outputs. See Figure 23 below for inputs wiring and Figure
24, page 39
for outputs wiring.

M

ENTER

UP

DOWN

ALARM

MENU

OE370-26-RSMV

REFRIGERANT

SYSTEM MODULE V

AAON No.: V42440

E-BUS

E-BUS

+24

V

AC

GND

RELAY CONTACT
RATING IS 1 AMP

MAX @ 24 VAC

CONDENSER

COMP 1
COMP 2

EXPANSION

VALVE 1

SUCTION

PRESSURE

SENSOR

HEAD

PRESSURE

SENSOR

COIL TEMP

SENSORS

BINARY
INPUTS

EXPANSION

VALVE 2

ANALOG

OUTPUTS

BLACK

+5 V

+5 V

COIL TEMP 1

COMP STATUS 1

BLACK

MOD COMP SIG

CONDENSER FAN SIG

WHITE

SP

HP

COIL TEMP 2

COMP

2

STATUS

GND

GND

TEMP 3

OUTSIDE COIL TEMP. SW
BIN 4

GND

GND

WHITE

RED

RED

GND

GREEN

GREEN

REVERSING VALVE

COMMON

RELAY OUTPUT

TERMINALS

www.aaon.com

WattMaster Overlay #000065 Rev 1A

SW

SP

GND

+V

BK

RD
WH

HP

GND

+V

BK

RD
WH

SUCTION PRESSURE

SENSOR

HEAD PRESSURE

SENSOR

(BY OTHERS)

REFRIGERANT SYSTEM MODULE

FOR VFD COMPRESSORS

(RSMV)

COIL

TEMP. 2 SENSOR

(SUCTION LINE)

TEMP1

GND

TEMP2

COMPRESSOR STATUS 1

COMPRESSOR STATUS 2

BIN1
BIN2

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
RSMV = 18 VA

GND

COIL (SUCTION LINE)

TEMP. 1 SENSOR

RSMV Inputs & Outputs Wiring

Figure 23: RSMV Inputs Wiring

The RSMV Module provides the following:

•

Controls the Compressors to satisfy the Supply Air

Temperature Setpoint (Supply Air Temperature sent

by VCC-X Controller) during Cooling Mode. During

Dehumidifi cation Mode, it controls the Compressors

to the Suction (Saturation) Temperature Setpoint

•

Modulates the Condenser Fan to maintain the Head

Pressure

Setpoint

•

Modulates the Expansion Valves to maintain the

Superheat

Setpoint

•

Provides alarms and safeties for the compressor and

condenser

operation.

•

Contains a 2 x 8 LCD character display and 4

buttons that allow for status display, setpoint changes,

and

confi guration changes.