Appendix a - system configurations, Vcc-x controller technical guide, Oe271 pressure sensor testing – Orion System VCC-X Controller User Manual

Page 79

Advertising
background image

VCC-X Controller Technical Guide

APPENDIX A - SYSTEM CONFIGURATIONS

79

OE271 Pressure Sensor Testing Instructions
Use the voltage column to check the Duct Static Pressure Sensor
while connected to powered controllers. Read voltage with meter
set on DC volts. Place the “-” (minus) lead on the GND terminal and
the “+” (plus) lead on the 0-5 pin terminal on (TP) with the jumper
removed. Be sure to replace the jumper after checking.

OE258-01 Building Pressure Sensor Testing

Instructions
Use the voltage column to check the Building Static Pressure Sensor
while connected to a powered expansion module. Read voltage with
meter set on DC volts. Place the “-” (minus) lead on terminal labeled
GND and the “+” lead on terminal AIN4 on the Analog Input/Output
Expansion Module.

OE271 & OE258-01 Pressure Sensor Testing

OE271 Pressure Sensor Testing

The table below is used to troubleshoot the OE271 Duct Static
Pressure Sensors.

OE258-01 Pressure Sensor Testing

The table below is used to troubleshoot the OE258-01 Building
Pressure Sensors.

OE271 Duct Static Pressure Sensor

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

0.00

0.25

2.60

2.33

0.10

0.33

2.70

2.41

0.20

0.41

2.80

2.49

0.30

0.49

2.90

2.57

0.40

0.57

3.00

2.65

0.50

0.65

3.10

2.73

0.60

0.73

3.20

2.81

0.70

0.81

3.30

2.89

0.80

0.89

3.40

2.97

0.90

0.97

3.50

3.05

1.00

1.05

3.60

3.13

1.10

1.13

3.70

3.21

1.20

1.21

3.80

3.29

1.30

1.29

3.90

3.37

1.40

1.37

4.00

3.45

1.50

1.45

4.10

3.53

1.60

1.53

4.20

3.61

1.70

1.61

4.30

3.69

1.80

1.69

4.40

3.77

1.90

1.77

4.50

3.85

2.00

1.85

4.60

3.93

2.10

1.93

4.70

4.01

2.20

2.01

4.80

4.09

2.30

2.09

4.90

4.17

2.40

2.17

5.00

4.25

2.50

2.25

OE258-01 Building Pressure Sensor

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

-0.25

0.00

0.01

2.60

-0.24

0.10

0.02

2.70

-0.23

0.20

0.03

2.80

-0.22

0.30

0.04

2.90

-0.21

0.40

0.05

3.00

-0.20

0.50

0.06

3.10

-0.19

0.60

0.07

3.20

-0.18

0.70

0.08

3.30

-0.17

0.80

0.09

3.40

-0.16

0.90

0.10

3.50

-0.15

1.00

0.11

3.60

-0.14

1.10

0.12

3.70

-0.13

1.20

0.13

3.80

-0.12

1.30

0.14

3.90

-0.11

1.40

0.15

4.00

-0.10

1.50

0.16

4.10

-0.09

1.60

0.17

4.20

-0.08

1.70

0.18

4.30

-0.07

1.80

0.19

4.40

-0.06

1.90

0.20

4.50

-0.05

2.00

0.21

4.60

-0.04

2.10

0.22

4.70

-0.03

2.20

0.23

4.80

-0.02

2.30

0.24

4.90

-0.01

2.40

0.25

5.00

0.00

2.50

Table 7: Duct Static Pressure/Voltage for
OE271 Duct Static Pressure Sensors

Table 8: Building Static Pressure/Voltage for
OE258-01 Building Pressure Sensors

Advertising
This manual is related to the following products: