Lcd display screens, Main screens map and modgas screens, Modgas-xwr technical guide – Orion System MODGAS-XWR User Manual

Page 15: Main modgas screens, Protected screens map

Advertising
background image

MODGAS-XWR Technical Guide

LCD DISPLAY SCREENS

15

Main Screens Map and MODGAS Screens

Main MODGAS Screens

Refer to the following map when navigating through the Main Screens.
From the MODGAS Stepper Screen, press

<ENTER>

to scroll through

the screens.

MODGAS

STEPPER

S/A or COMM

MODE

SOFTWARE

1060 V.XXX

ADDRESS
1 (138)

In Stand-Alone Mode, the screen will only display S/A MODE.

In Communications Mode, the screen will display COMM MODE and the
items below will scroll through the screen:

1. Number of good packets being received. This will roll over after 9999.
Example: +XXXX

2. Number of checksum errors. This will stop at 9999. Example: C-XXXX

3. Number of packet length errors. This will stop at 9999 until power is
cycled. Example: P-XXXX

CURRENT BOARD ADDRESS

Number in parentheses is E-BUS address.

CURRENT SOFTWARE VERSION

You can access the protected screens from this screen by holding the

<UP> button for 5 seconds.

CONFIG

DIAGNSTC

ENTER TO

EXIT

Protected Screens Map

Refer to the following map when navigating through the LCD Protected
Screens. From the MODGAS STEPPER Screen, press the

<ENTER>

twice until you get to the SOFTWARE Screen. Then hold the

<UP>

button for 5 seconds. To scroll through the rest of the screens, press the

<MENU>

button.

SOFTWARE

1060 V.XXX

Hold for 5 seconds.

MODGAS

STEPPER

S/A MODE

# STAGES

T=2 M=2

NUMBER OF STAGES CONFIGURED

T = Total stages fi xed and modulating

M = Total modulating stages