Lcd display screens, Main screens map and modgas screens, Modgas-xwr technical guide – Orion System MODGAS-XWR User Manual
Page 15: Main modgas screens, Protected screens map

MODGAS-XWR Technical Guide
LCD DISPLAY SCREENS
15
Main Screens Map and MODGAS Screens
Main MODGAS Screens
Refer to the following map when navigating through the Main Screens.
From the MODGAS Stepper Screen, press
<ENTER>
to scroll through
the screens.
MODGAS
STEPPER
S/A or COMM
MODE
SOFTWARE
1060 V.XXX
ADDRESS
1 (138)
In Stand-Alone Mode, the screen will only display S/A MODE.
In Communications Mode, the screen will display COMM MODE and the
items below will scroll through the screen:
1. Number of good packets being received. This will roll over after 9999.
Example: +XXXX
2. Number of checksum errors. This will stop at 9999. Example: C-XXXX
3. Number of packet length errors. This will stop at 9999 until power is
cycled. Example: P-XXXX
CURRENT BOARD ADDRESS
Number in parentheses is E-BUS address.
CURRENT SOFTWARE VERSION
You can access the protected screens from this screen by holding the
<UP> button for 5 seconds.
CONFIG
DIAGNSTC
ENTER TO
EXIT
Protected Screens Map
Refer to the following map when navigating through the LCD Protected
Screens. From the MODGAS STEPPER Screen, press the
<ENTER>
twice until you get to the SOFTWARE Screen. Then hold the
<UP>
button for 5 seconds. To scroll through the rest of the screens, press the
<MENU>
button.
SOFTWARE
1060 V.XXX
Hold for 5 seconds.
MODGAS
STEPPER
S/A MODE
# STAGES
T=2 M=2
NUMBER OF STAGES CONFIGURED
T = Total stages fi xed and modulating
M = Total modulating stages