Lcd display screens, Force valve & confi guration screens, Modgas-xwr technical guide 18 – Orion System MODGAS-XWR User Manual
Page 18: Force valve screens, Confi guration screens

LCD DISPLAY SCREENS
MODGAS-XWR Technical Guide
18
Force Valve & Confi guration Screens
Force Valve Screens
Refer to the following map when navigating through the Force Valve
Screens. From the FORCE VALVE Screen, press
<ENTER>
. At the
V1 and V2 FORCE ON/OFF screens, press the
<UP>
arrow key to
turn the FORCE MODE on and press the
<DOWN>
arrow key to turn
the FORCE MODE off. Use the
<UP>
and
<DOWN>
arrow keys to
increase and decrease the percentage.
FORCE
VALVES
V1 FORCE
ON/OFF
FORCE V1
X%
FORCE VALVE 1 PERCENTAGE
This screen only appears when Valve 1 Force is on.
This screen below will appear when the Force Mode times out after 1
hour.
FORCE
TIMEOUT
Press the
<UP> button to turn the Force Mode on. Press the <DOWN>
button to turn the Force Mode off.
Press the
<UP> button to increase the percentage. Press the <DOWN>
button to decrease the percentage.
NOTE: When you turn the Force Mode back off or after 1 hour has
elapsed, the valve will reinitialize to zero.
FORCE MODE TIME OUT
V2 FORCE
ON/OFF
FORCE V2
X%
FORCE VALVE 2 PERCENTAGE
This screen only appears when Valve 2 Force is on.
Press the
<UP> button to turn the Force Mode on. Press the <DOWN>
button to turn the Force Mode off.
Press the
<UP> button to increase the percentage. Press the <DOWN>
button to decrease the percentage.
NOTE: When you turn the Force Mode back off or after 1 hour has
elapsed, the valve will reinitialize to zero.
Confi guration Screens
Refer to the following map when navigating through the Confi guration
Screens. From the CONFIG Screen, press
<ENTER>
to scroll through
the screens and change setpoints. Use the
<UP>
and
<DOWN>
arrow
keys to change your selections. Press
<ENTER>
to save any changes.
CONFIG
# STAGES
1 TO 15
NUMBER OF TOTAL STAGES
Range is 1 to 15. Default is 2.
# MOD STG
1 OR 2
NUMBER OF MODULATING STAGES
Range is 1 or 2. Default is 2.