LCD DISPLAY SCREENS

MODGAS-XWR Technical Guide

18

Force Valve & Confi guration Screens

Force Valve Screens

Refer to the following map when navigating through the Force Valve
Screens. From the FORCE VALVE Screen, press

<ENTER>

. At the

V1 and V2 FORCE ON/OFF screens, press the

<UP>

arrow key to

turn the FORCE MODE on and press the

<DOWN>

arrow key to turn

the FORCE MODE off. Use the

<UP>

and

<DOWN>

arrow keys to

increase and decrease the percentage.

FORCE

VALVES

V1 FORCE

ON/OFF

FORCE V1

X%

FORCE VALVE 1 PERCENTAGE

This screen only appears when Valve 1 Force is on.

This screen below will appear when the Force Mode times out after 1
hour.

FORCE

TIMEOUT

Press the

<UP> button to turn the Force Mode on. Press the <DOWN>

button to turn the Force Mode off.

Press the

<UP> button to increase the percentage. Press the <DOWN>

button to decrease the percentage.

NOTE: When you turn the Force Mode back off or after 1 hour has
elapsed, the valve will reinitialize to zero.

FORCE MODE TIME OUT

V2 FORCE

ON/OFF

FORCE V2

X%

FORCE VALVE 2 PERCENTAGE

This screen only appears when Valve 2 Force is on.

Press the

<UP> button to turn the Force Mode on. Press the <DOWN>

button to turn the Force Mode off.

Press the

<UP> button to increase the percentage. Press the <DOWN>

button to decrease the percentage.

NOTE: When you turn the Force Mode back off or after 1 hour has
elapsed, the valve will reinitialize to zero.

Confi guration Screens

Refer to the following map when navigating through the Confi guration
Screens. From the CONFIG Screen, press

<ENTER>

to scroll through

the screens and change setpoints. Use the

<UP>

and

<DOWN>

arrow

keys to change your selections. Press

<ENTER>

to save any changes.

CONFIG

# STAGES

1 TO 15

NUMBER OF TOTAL STAGES

Range is 1 to 15. Default is 2.

# MOD STG

1 OR 2

NUMBER OF MODULATING STAGES

Range is 1 or 2. Default is 2.