Networked single loop system, System manager touch screen operator interface, Systems design technical guide 10 – Orion System Systems Design User Manual
Page 10: System manager touch screen ii

Zone
Zone
Networked Single Loop System
Systems Design Technical Guide
10
Networked Single Loop with HVAC Unit
Controller and Non-Modular VAV/Zone
Controllers with MiniLink PD Using
Modular System Manager
System Manager Touch Screen II
The System Manager Touch Screen II (SMTS II) provides a direct
graphic-enhanced, menu-driven link to view the status and to adjust
the setpoints of any controller on the Orion Controls system. The
SMTS II utilizes a graphical touch screen menu system with easy
to understand menu trees and icons and noncryptic plain English
language messages. It is housed in an off-white plastic housing that
is suitable for most decors and that is designed for permanent wall
mounting in the space or equipment room. In order for the ALARM
Button to operate on the SMTS II Main Screen with a Networked
Single Loop system, you will need to purchase and install a MiniLink
PD in addition to the System Manager TS II.
Networked Single Loop with HVAC Unit
Controllers with MiniLink PD
Using System Manager TS II
Networked Single Loop with HVAC Unit
Controller and Modular VAV/Zone Controllers
with MiniLink PD Using System Manager TS II
Networked Single Loop with HVAC Unit
Controller and Non-Modular VAV/Zone
Controllers with MiniLink PD Using
System Manager TS II
System Manager Touch Screen Operator Interface
EPROM
U3
U5
RAM
C
X2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILIPS
D
1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R27
R
31
D4
G
N
D
24V
A
C
T
B1
D5
C11
U12
LED 2
POWER
V1
R25
R26
C7
C
X15
CX
13
PROC.
DRIVER
LOOP
DRIVER
LOCAL LOOP
G
N
D
AIN 2
AIN 1
+5V
TB2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
T
B
3
U
15
LD5
LD6
U
13
C8
LED 1
RV1
R4
VR
EF
CX
2
U11
YS101900PMINILINK
POLLING
DEVICE
REV. 1
OFF
1 2 4 8 16 32
C
X14
NETWORK
DRIVER
RN3
S
H
LD
S
H
LD
T
T
TB
4
R
R
U
14
NETWORK
LOOP
P
5
A
D
D
P3
R
24
LD4
C9
U10
RN2
SW1
R30
X2
R29
R28
C10
U6
C
X6
C
X1
U7
U1
X1
C
3
C1
R
3
CX7
SYSTEM MANAGER
TOUCH SCREEN II
MINILINK PD
HVAC CONTROLLER - TYP.
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
HVAC CONTROLLER - TYP.
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
HVAC CONTROLLER - TYP.
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
TB2
VA
C
F
1
25
4A
24
SH
LD
T
R
PO
W
ER
LD1
T
B1
C
1
P
OW
E
R & CO
M
M
D
IS
T
. BO
AR
D
Y
S101
856
R
EV
. 0
P5
P4
P3
P1
D1
V1
R1
P
2
COMMPIN
POWER & COMM
OUT
EPROM
U3
U5
RAM
C
X
2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILIPS
D
1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R2
7
R3
1
D4
GN
D
24V
A
C
TB
1
D5
C11
U12
LED 2
POWER
V1
R
25
R
26
C7
C
X
15
C
X
13
PROC.
DRIVER
LOOP
DRIVER
LOCAL LOOP
G
N
D
AIN
2
AIN
1
+
5V
TB
2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
TB
3
U
1
5
LD5
LD6
U
1
3
C8
LED 1
RV1
R
4
VR
E
F
CX
2
U11
YS101900PMINILINK
POLLING
DEVICE
REV. 1
OFF
1 2 4 8 16 32
C
X
14
NETWORK
DRIVER
RN3
S
HLD
SH
LD
T
T
TB
4
R
R
U
14
NETWORK
LOOP
P
5
AD
D
P3
R
24
LD4
C9
U10
RN2
SW1
R30
X2
R29
R28
C10
U6
C
X
6
C
X1
U7
U1
X1
C
3
C
1
R
3
CX7
MINILINK PD
HVAC CONTROLLER
POWER/COMM BOARD
VAV/ZONE
CONTROLLER - TYP
SYSTEM MANAGER
TOUCH SCREEN II
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANSION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
ON
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANSION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
ON
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANSION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
POWER/
CO
MM
STA
T
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
ON
EPROM
PAL
485
REC
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
NON-MODULAR
VAV/ZONE CONTROLLER - TYP
EPROM
U3
U5
RAM
C
X2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILIPS
D
1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R27
R
31
D
4
G
N
D
24V
A
C
TB
1
D5
C11
U12
LED 2
POWER
V
1
R
25
R
26
C7
C
X15
CX
13
PROC.
DRIVER
LOOP
DRIVER
LOCAL LOOP
G
N
D
A
IN
2
A
IN
1
+5V
TB
2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
TB
3
U
15
LD5
LD6
U
13
C8
LED 1
RV1
R
4
V
R
E
F
C
X
2
U11
YS101900PMINILINK
POLLING
DEVICE
REV. 1
OFF
1 2 4 8 16 32
C
X14
NETWORK
DRIVER
RN3
S
H
LD
SH
LD
T
T
T
B
4
R
R
U14
NETWORK
LOOP
P5
A
D
D
P
3
R24
LD4
C9
U10
RN2
SW1
R30
X2
R29
R28
C10
U6
C
X6
CX
1
U7
U1
X1
C
3
C
1
R
3
CX7
SYSTEM MANAGER
MINILINK PD
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
ON
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EXP
ANS
IO
N
D'S
TA
T
SP
AC
ES
EN
SO
R
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
ON
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
HVAC CONTROLLER - TYP.
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR
NON-MODULAR
VAV/ZONE CONTROLLER - TYP
EPROM
U3
U5
RAM
C
X
2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILIPS
D
1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R2
7
R3
1
D4
G
N
D
24V
A
C
TB
1
D5
C11
U12
LED 2
POWER
V1
R
25
R
26
C7
C
X
15
C
X
13
PROC.
DRIVER
LOOP
DRIVER
LOCAL LOOP
G
N
D
A
IN 2
A
IN 1
+5
V
TB
2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
TB
3
U
1
5
LD5
LD6
U
1
3
C8
LED 1
RV1
R
4
VR
E
F
CX
2
U11
YS101900PMINILINK
POLLING
DEVICE
REV. 1
OFF
1 2 4 8 16 32
C
X
14
NETWORK
DRIVER
RN3
S
HLD
SH
LD
T
T
TB
4
R
R
U
1
4
NETWORK
LOOP
P
5
AD
D
P3
R2
4
LD4
C9
U10
RN2
SW1
R30
X2
R29
R28
C10
U6
C
X
6
C
X1
U7
U1
X1
C
3
C
1
R
3
CX7
MINILINK PD
SYSTEM MANAGER
TOUCH SCREEN II
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANS
ION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
V
A
VZ 2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
AC
R
SHLD
T
TB2
REC
VAV
Z
2
FOR ENCL.
W/TERM BLKS
YS102218
REV2
EX
PANSION
D'S
TAT
SPACE
SENSOR
MADE IN USA
W
A
TTMASTER CONTROLS INC
HI(V
A
V
)
LOW(VVT)
VEL
OC
IT
Y
ADDRESS
OFF
O
N
EPROM
PAL
485
DR
V
EEPR
OM
93C66
(-)LO
GND
OUT
IN
setra
26311R5WD4MZZCWM1
RANGE: 0- 1.5"WC
Exc: 5 VDC
Output: .25 - 4.25 VDC
S/N: 2620413 2705
ACTU
ATOR
1
0
OE282
TB3
ST
A
T
GND
24V
A
C
R
SHLD
T
TB2
REC
HVAC CONTROLLER, TYP.
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102033-01
OE332-23-VCMX-A VCM-X CONTROLLER
WA
RN
IN
G
OBSERVE
POLARITY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
WattMaster Label
#LB102073-01-A
Rev.: 1A
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AAON No.:
V07150
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= RAT (RETURN AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= ECONOMIZER (2-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
LED BLINK CODES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
OAT FAIL
2
2
SPC FAIL
3
2
MODULE ALARM
4
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
E-BUS
CONNECTOR