CLEARANCES


It is of utmost importance that the clearances to combustible material be scrupulously
respected upon installation of the stove you have selected. Refer to the tables below :

Figure 6: Clearances to combustibles

CANADA

Single pipe / Double pipe

Model A

B

C

D

E

F

HT-1600

15/12 16/16 12/10

20.8/17.8 28.7/28.7 25.2/23.2

HT-2000 19/10

19/14

11/8

25.4/16.4 33.1/28.1 25.5/22.5

USA

Single pipe / Double pipe

Model A

B

C

D

E

F

HT-1600

15/12 16/16 12/10

20.8/17.8 28.7/28.7 25.2/23.2

HT-2000 19/10

19/14

11/8

25.4/16.4 33.1/28.1 25.5/22.5


• Floor to ceiling height must be at least 7' (84") in all cases.
• The clearance between the flue pipe and a wall are valid only for vertical walls and for

vertical flue pipe.

• The flue pipe must not go through roof trussing, an attic, a wardrobe or similar spaces;

neither a floor or combustible partition.

• A flue pipe crossing a combustible wall must have a clearance of 18" minimum.
• To reduce flue pipe clearances from combustible materials, contact your local safety

department.