SNORKEL TERMINATION INSTALLATION
Recommended Applications:
• Installations requiring a vertical rise on building exterior

• Any installation using snorkel termination to achieve one foot above ground

Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If installing snorkel termina-

tion below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back fill

around snorkel termination.

VENTING INSTALLATION INSTRUCTIONS

Continued

12"

Minimum

Snorkel

Termination

Snorkel

Termination

12"

Minimum

Snorkel Termination

Wall

Firestop

90° Elbow

45°

Elbow

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

12"

Minimum

Adequate

Drainage

HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS
The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.

45° Elbow

Venting with Two 90° Elbows

Vertical (V) Horizontal Horizontal (H

1

) +

(H

1

)

Horizontal (H

2

)

5' min.

2' max.

6' max.

6' min.

4' max.

12' max.

7' min.

6' max.

18' max.

8' min.

8' max.

20' max.

20' max.

8' max.

20' max.

Figure 17 - Horizontal Termination Configuration for Venting

Using Two 90° Elbows

45° Elbow

Figure 18 - Horizontal Termination Configuration for Venting

Using Two 90° Elbows with Termination at 90° with Fireplace

Venting with Two 90° Elbows

Vertical (V) Horizontal (H

1

)

Horizontal (H

2

)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

20' max.

20' max.