Remko rvd...dc – REMKO RVD xxx DC User Manual

Page 30

Advertising
background image

Problem display by blinker code

LED

Operation

LED

Timer

LED

Defrost

LED

Alarm

Display

outdoor

unit

Cause

Required action

E0

EEPROM error

Check EEPROM

E2

Communication error between PCBs
outdoor unit & indoor unit

Check electrical connection
leads

E3

Communication error between out-
door unit main board & outdoor unit
inverter board

Check wiring

E4

Outdoor temp sensor on outdoor com-
ponent tripped

Check resistance and tem-
perature on sensor

E5

Overvoltage compressor

Check compressor voltage

P0

Excessive temperature compressor

Allow compressor to cool

P1

High pressure sensor has triggered

Check refrigerant pressure

P2

Low pressure sensor has responded

Check refrigerant pressure

P3

Compressor power consumption too
high

Check compressor power
consumption

P4

Compressor discharge gas over 105°C

Clean liquefier, check refrig-
erant circuit

P5

Liquefier temperature over 65°C

Clean liquefier, check refrig-
erant circuit

P6

Voltage protection main board outdoor
unit

Check voltage

flashes
rapidly

Sensor air circulation / sensor liquefier
tripped

Check resistance

flashes
rapidly

Communication error between outdoor
unit & indoor unit

Check electrical connection
leads

flashes
rapidly

Mode malfunction

Switch system off

flashes

slowly

flashes

slowly

flashes

slowly

flashes

slowly

Sensor liquefier / outdoor temp faulty
or not correctly connected

Read off error code on
outdoor unit
Check sensors

flashes
rapidly

Condensate pump float switch faulty

Check condensate pump
and float switch

REMKO RVD...DC