REMKO CMF - DUO

Overview of faults and their possible causes for the indoor unit charge pump

Indicator light does not illuminate

Indicator light lights up permanently

Indicator light flashes

Green LED Red LED

Fault

Meaning

Remedial measures

The pump does not run

A fuse or circuit breaker in the

installation has blown/tripped.

Replace the fuse/reset the circuit

breaker. Check whether there is a

power supply in the specified area.

The residual current device (RCD)

or fault voltage circuit breaker was

tripped.

Reset the RCD or circuit breaker.

Check whether there is a power

supply in the specified area.

The pump may be defective.

Replace the pump.

The pump does not run

The pump was switched off.

Possible causes:

1. By the button

.

2. External ON/OFF switch

switched off

3. Using the bus signal.

1. Switch on the pump using the

button.

2. Switch on the external ON/OFF

switch.

3. Switch on the pump using

the bus signal.

The pump was switched

off due to a fault.

Power failure.

Check whether there is a power

supply in the specified area.

Pump jammed and/or dirty.

Disassemble pump and clean

The pump may be defective.

Replace the pump.

The pump runs, but is

faulty.

Pump is faulty but still able to

continue running.

Try acknowledging the fault message

by briefly switching off the power
supply or by pressing the

,

or

button.

The pump was set to

STOP and is faulty.

Pump is faulty but still able to

continue running (set to STOP).

The system makes

noises.

Air in the system.

Bleed the system

Delivery rate is too high.

Reduce the target value and if

AUTO

ADAPT

or Constant pressure.

Delivery pressure.

Reduce the target value and if

AUTO

ADAPT

or Proportional pressure.

The pump makes

noises.

Supply pressure is too low.

Increase supply pressure and/or check

the gas volume in the expansion

vessel (if present).

Air in the pump

Adjust the pump setting by pressing
and holding the

button. After the

pump has been bled press the

and

buttons to switch back to normal

mode.

CAUTION

: The pump must never be

allowed to run dry.