REMKO HEAT PUMP MANAGER

Designation

Value range

Factory setting

Description

Hysteresis WW

3. 0 K - 3 0. 0 K

5. 0 K

Setting the hot water hysteresis.

Water heating starts if the temperature in the hot water tank
(sensor F-6) falls below the target temperature (see user

hot water

T-WW target) by the temperature set here.

Water heating ends if the tank reaches the set target
temperature
(in the anti-legionella mode the target temperature is set to
65°C, see user

hot water

anti-legionella).

WW lag

0 0 - 3 0

0 1

Setting the pump lag period.


The pump lag period (5 min.) is extended by the value set
here.

The indoor unit's charge pump continues to run for
another 5 minutes after the heat pump has been shut off
(independent of the period set here).
The lag period is interrupted if there is a demand for heat in
a heating circuit.
An activated charge pump lock can likewise lead to an
interruption of the lag function.

TH inlet

On / Off

Off

Activating the water heating by means of thermostat or sensor.

• On (water heating by means of thermostat)
In the event of a short circuit, water heating is started at the
tank sensor's connection terminals. It ends if the short circuit
has been corrected.

• Off (water heating by means of tank sensor).

Thermal function

On / Off

Off

Activating the aligned target temperature.

The target temperature during water heating is arrived at by
adding the current tank temperature [sensor 6] to T-WE WW.

Charging

On / Off

Off

Activating the charging function
(only possible with sensor 12 = T-WW U).

Water heating with activation of this function (charging =
ON) is not ended until the sensor F 12 (not F 6) has reached
the warm water target temperature.

Hot water - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued