Figure 4.6 latching alarms/leak configuration – RLE LD2000 User Manual
Page 34

www.rletech.com
34
970.484.6510
4
Web Interface
Figure 4.6 Latching Alarms/Leak Configuration
Resistance Per Foot
The resistance per foot (or meter) of cable determines the unit's
ability to accurately detect the cable length installed and calculate
distances to leaks. The default setting is 2.800 ohms and should
not be changed for any RLE cable; parts SC-10, SC-25, SC-50, and
SC-100 are all built to specifications of 2.8 ohms per foot.
Measurement
Display
The type of units that are displayed on the LD2000. Select either
feet or meters to calibrate the unit to the preferred unit of measure.
Latching Alarms
This option selects the latching ability for the alarm notifications of
the unit. Latching alarms will hold the unit in an alarm state, even
after the condition has been cleared, until someone presses the
Reset button, located on the front of the physical LD2000 unit.
Table 4.1 Link Settings Menu Settings (continued)
Leak Settings Menu
Option
Description