Web Interface

Figure 4.6 Latching Alarms/Leak Configuration

Resistance Per Foot

The resistance per foot (or meter) of cable determines the unit's

ability to accurately detect the cable length installed and calculate

distances to leaks. The default setting is 2.800 ohms and should

not be changed for any RLE cable; parts SC-10, SC-25, SC-50, and

SC-100 are all built to specifications of 2.8 ohms per foot.

Measurement

Display

The type of units that are displayed on the LD2000. Select either

feet or meters to calibrate the unit to the preferred unit of measure.

Latching Alarms

This option selects the latching ability for the alarm notifications of

the unit. Latching alarms will hold the unit in an alarm state, even

after the condition has been cleared, until someone presses the

Reset button, located on the front of the physical LD2000 unit.

Table 4.1 Link Settings Menu Settings (continued)

Leak Settings Menu

Option

Description