Slc300, Service diagnosis – Scotsman SLC300 User Manual

Page 19

Advertising
background image

Service Diagnosis:

SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

No ice is made, nothing operates

Unit off, due to no power

Restore power

Unit off, due to ICE/OFF/WASH
switch in OFF position

Switch ICE/OFF/WASH switch to
ICE

Unit off, due to bin thermostat
open

Check temperature at bin
thermostat bracket, if warmer than
40

o

F., thermostat should be

closed. Adjust/replace thermostat.

Water cooled unit off, due to high
pressure cut out open

Lack of water to condenser,
check water supply and water
regulating valve.

No ice, compressor off

No cooling due to compressor not
operating

Check compressor for voltage,
continuity, and operation. Check
starting components. Replace if
found to be faulty.

Check temperature of
compressor, if hot may be lack of
refrigerant, defective TXV or
compressor

No ice is made, compressor is
operating

No water due to water turned off.

Reconnect water supply

No water due to water filter
plugged.

Replace water filter

No water due to strainer screen
plugged

Clean out inlet screen

No water due to inlet water valve
will not open

Replace valve

Water in reservoir, but no water
over evaporators

Water pump does not work,
replace pump

No cooling at evaporator due to
hot gas valve leaking thru

Replace hot gas valve

No cooling at evaporator due to
fan not turning

Check & replace fan motor.

Fan and pump do not have
power; hot gas valve opens and
closes.

Coil or relay open, replace relay.

No cooling at evaporator due to
dirty condenser

Clean condenser

No cooling due to compressor not
pumping

Check system pressures, replace
compressor if not pumping

SLC300

November 1994

Page 19