Seaward AGL-5 User Manual

Page 2

Advertising
background image

2 Proving

•

Connect the one probe to the BLACK
terminal.

•

Connect the other probe to the RED terminal.

•

Press the probe down onto the RED terminal
as shown below to operate the internal
micro-switch.

•

Confirm that the neon illuminates indicating
the test voltage is active.

•

Confirm that the LED indicators in the AGL-5
illuminate.

•

Disconnect both probes from the proving
unit.







3 Specifications

Maximum Working
Voltage

5000V AC/DC

Threshold voltage

50V AC / 70V DC

Operating Current

<3.5mA AC/DC at max
working voltage

Indicator

High intensity LED with
polarizing filter

Handle length

160mm

Overall Length

530mm

Probe tip length

38mm

Hand guard height

>10mm over 70%
circumference

Length of insulation
between contact
electrode and hand-
guard

574mm

Un-insulated contact
electrode length

5mm

Contact Electrode
diameter

3mm

Lead length between
probes

0.8m triple insulated cable

Construction

High Impact, total
encapsulation

Compliance

BS EN 61243-2:1998













4 Maintenance

Clean only with a dry cloth; do not use solvents.
Before use, ensure unit is clean and dry; visually
inspect test terminals and case. Any damage must be
rectified to preserve user safety.



5 Service and Calibration

To

maintain

the

specified

performance,

the

instrument must be verified at regular intervals by
either the manufacturer or an authorised Seaward
Service Agent. We recommend a calibration period
of one year.
For help or advice on Service and Calibration
contact:

Service Department
Seaward Electronic
Bracken Hill
South West Industrial Estate
Peterlee
Co Durham SR8 2SW
England

Tel: 0191 5878739 / 0191 5878737
Email:

[email protected]

Web:

www.seaward.co.uk