SPECIFICATION
Earth Bond Test
AC Test Currents ...................
6A, 12A, 20A, 25A @ 6V RMS (nominal)
Corresponds to Type A earth continuity tester as
defined in Electricity at Work Regulations 1989.
...............................................
100mA @ 500mV RMS (nominal)
Corresponds to Type B earth continuity tester as
defined in Electricity at Work Regulations 1989.
...............................................
Electronically controlled constant current to ± 20%
accuracy.
Note: the current will only be controlled within an acceptable test load impedance.
Display Range ......................
0>1.999
Ω
Accuracy ...............................
± 10% or 1m
Ω
whichever is the greater. ± 2 counts.
Note: Impedance of the earth connector will be significant at low impedances.
Resolution ............................
1m
Ω
Test Duration .......................
6 seconds nominal
Insulation Test
DC Test Voltage ..................
480V min, 600V max off load
Display Range .....................
10k
Ω
to 19.99M
Ω
Accuracy .............................
± 3% or 10k
Ω
(whichever is the greater) up to 15.00M
Ω
Resolution ...........................
10k
Ω
Test Duration ......................
6 seconds nominal
Fuse Test
AC Test Current .................
30 mA max, 9V o/c
Display ...............................
LED Indicator
Display Indication ...............
≤
1K
Ω
Protection ...........................
Internal Fuse
Supply Voltage
AC Supply ..........................
240V ± 10% @ 50Hz
Note: Some readings and specification figures are related to supply voltage variation
Physical Data
Dimensions ........................
250mm x 200mm x 150mm (approx)
Weight ................................
4 kilo (approx)
Temperature Range ...........
0° to 40°C (operating), -10° to 70°C (Storage)
............................................
Thermal cut-out will operate when internal
components attain 70°C in order to prevent damage
REPLACEMENT PARTS
Earth Lead .........................
207A915
Insulation Probe .................
207A918
FUSES
Plug Fuse ..........................
5A to BS 1362
There are no user serviceable parts within the unit.
Due to a policy of continuous development Seaward Electronic Limited reserves the right to alter equipment specification
and description outlined in this publication without prior notice and no part of this publication shall be deemed to be part of
any contract for the equipment unless specifically referred to as an inclusion within such contract.
211A557-B