Seaward 50 PrimeTest User Manual
Page 13

PrimeTest 50
Operating Instructions
11
3.3
Testing a Class II Appliance
x
Visually inspect the appliance and mains cord for
signs of damage.
x
If the appliance passes a visual inspection
proceed with the electrical tests.
x
Plug the earth test lead into the 4mm socket
on the PrimeTest 50 end panel.
x
Plug the appliance into the PrimeTest 50 front
panel mains socket
x
Connect the earth test probe to an exposed
metal part on the appliance.
x
If the Appliance under test has an ON/OFF
switch, make sure it is in the ON position.
x
Press the Class II test key
x
The PrimeTest 50 will now test Insulation
Resistance.
Note: The power switch on the appliance under
must be in the ON position to perform an
insulation test. If no appliance is detected
the PrimeTest 50 will display the following.
6
1
3