Sun Pumps MTR BLM-SB-103S-120Y User Manual
Page 9

1. After mounting the controller, switch the controller to the OFF position.
2. Verify all dip switches are off at this time.
3. Connect ground rod conductor to the controller chassis ground block.
4. Connect solar module frame ground conductor to controller chassis ground block.
5. Connect the green pump ground conductor to controller chassis ground block.
6. Connect pump motor leads to the corresponding “Pump Motor” terminals on the controller. Red to “Red”,
yellow to “Yellow” and black to “Black”.
7. Verify that the disconnect switch is in the off position. Connect the DC source supply negative (-), the
black conductor, to one of the controller terminals labeled “Negative” on the “Solar Array Input”. (NOTE:
The power should be connected to a disconnect and it should be in the OFF position before connecting
power to the controller).
8. Connect the DC source supply positive (+), the red conductor, to one of the controller terminals labeled
“Positive” on the “Solar Array Input”. (NOTE: The power should be connected to a disconnect and it
should be in the OFF position before connecting power to the controller).
9. Refer to the next section for “Remote Switch” and “Low Water Cutoff” connections as well as
“Adjustment Procedures” for configuration, if applicable.
10. At this point, all system components are installed and wired, double check conductor polarities, wire
termination tightness and controller configuration. With a DC volt meter check the array open circuit
voltage (Voc) on the array side of the disconnect switch and the module polarity. Record the Voc for
future reference. You may do this on the Before Calling Sun Pumps Worksheet near the end of this
manual. Check this voltage reading against the “Voc” range for your specific system in the chart below.
(Figure 3)
11. After you have verified the voltage and polarity, switch the disconnect switch on - if the polarity is correct
the first LED light will be on.
12. Turn the “On/Off “switch to the ON position. The system should be operational. If the system does not
start and turns on any error lights or gives you an error message, proceed to the troubleshooting guide.
- MTR BLM-SB-203S-180 MTR BLM-SB-303S-240 PCC-120BLS-M2 PCC-180BLS-M2 PCC-240BLS-M2 MTR-BLM-SF-153C-120 MTR-BLM-SF-153C-90Y MTR-BLM-SF-303C-180 MTR-BLM-SF-353C-240 MTR-BLM-SF-153J-120 MTR-BLM-SF-153J-90Y MTR-BLM-SF-303J-180 MTR-BLM-SF-353J-240 SCP 100-60-180 BV SCP 115-60-240 BV SCP 50-50-120 BC SCP 58-51-48 BC SCP 62-42-105 BC SCP 67-50-120 BC SCP 75-40-105 BC SCP 80-55-180 BC SCP 86-55-180 BV SCP 86-65-180 BC SCP 94-37-120 BV SJT05-90BT SIJ 0.55-900P-90 BT SIJ 2.3-750P-150 BT SIJ 2.6-450P-90 BT SIJ 3.28-260P-75 BT SIJ 0.67-1500P-120 BL SIJ 2.2-1000P-105 BL SIJ 3.4-160P-45 BL SIJ 2.2-1300P-135 BL SIJ 2.9-700P-105 BL SIJ 3-640P-135 BL SIJ 3.1-220P-60 BL SIJ 3.1-700P-120 BL SJT10-120BL SCB-10-150-120 BL SCB-10-150-180 BL SCB-10-200-180 BL SCB-10-220-180 BL SCB-10-265-180 BL SCB-21-350-240 BL SCB-22-165-120 BL SCB-22-185-180 BL SCB-22-250-180 BL SCB-22-95-120 BL SCS 10-210-120Y BL SCS 10-440-180 BL SCS 12-127-60 BL SCS 12-160-120Y BL SCS 12-265-120 BL SCS 12-375-180 BL SCS 125-32-120 BL SCS 130-32-180 BL SCS 14-370-240 BL SCS 142-32-180 BL SCS 150-37-240 BL SCS 17-280-180 BL SCS 18-105-120Y BL SCS 20-180-120 BL SCS 20-190-180 BL SCS 20-90-120Y BL SCS 20-350-240 BL SCS 22-300-240 BL SCS 26-80-120Y BL SCS 30-130-120 BL SCS 30-165-180 BL SCS 30-240-240 BL SCS 44-80-120 BL SCS 45-116-180 BL SCS 50-110-240 BL SCS 7.5-250-120Y BL SCS 71-70-180 BL SCS 8-410-120 BL SCS 8-500-180 BL SCS 80-70-240 BL SCS 87-70-240 BL