1 alarm indication, 2 out of range indication, 3 sensor break indication – Super Systems 3L Series User Manual
Page 14: 4 operator parameters in level 1, Alarm indication, Out of range indication, Sensor break indication, Operator parameters in level 1

Operations Manual
Series 3L
14
3.3.1 Alarm Indication
Up to three alarms can be configured. If any alarm
occurs, the red ALM beacon will flash. A scrolling text
message will describe the source of the alarm (for
example, ALARM 1 HIGH). Any output attached to the
alarm will operate.
Press
and
(Ack) together to acknowledge the alarm
If the alarm is still present, the ALM beacon will light
continuously.
By default alarms are configured as non-latching, de-
energized in alarm. If you require latched alarms,
please refer to the engineering handbook.
3.3.2 Out of Range Indication
If the input is too high, HHHHH will be displayed.
If the input is too low, LLLLL will be displayed.
3.3.3 Sensor Break Indication
An alarm condition (
S.br) is indicated if the sensor or
the wiring between sensor and indicator becomes
open circuit.
For a PRT input, sensor break is indicated if any one of
the three wires is broken.
For mA input, sensor break will not be detected due to
the load resistor connected across the input terminals.
For Volts input, sensor break may not be detected due
to the potential divider network connected across the
input terminals.
3.4 Operator Parameters in Level 1
Operator level 1 is designed for day to day operation of
the indicator, and access to these parameters is not
protected by a pass code.
Press
to step through the list of parameters.
The
mnemonic of the parameter is shown in the lower
display. After five seconds, a scrolling text description
of the parameter appears.
The value of the parameter is shown in the upper
display. In level 1 the value is read only.
The parameters that appear depend upon the
functions configured. They are:
Parameter
Mnemonic
Scrolling
text and
Description
Availability
HIGH
PEAK HIGH
This is the highest reading
that the indicator has
recorded since switch on
or since it was reset
LOW
PEAK LOW
This is the lowest reading
that the indicator has
recorded since switch on
or since it was reset
A1 (----)
ALARM 1
SETPOINT
(----) shows the type of
alarm configured. For
example: HI, LO, ROC.
This parameter sets the
alarm thresholds.
A2 (----)
ALARM 2
SETPOINT
A3 (----)
ALARM 3
SETPOINT
A4 (----)
ALARM 4
SETPOINT