ZONE_OFF
The
Zone Offset
opcode is used to set an offset to be added to the set point sent to a specific
zone. Temperature, atmosphere, or both can be offset. The same loop (furnace) can have
different offsets for each zone. The zones must be defined in the zone configuration.
For example, a pit furnace has three zones: top, middle, and bottom.
The zones could be defined as:
top = zone 1,
middle = zone 2 ,
bottom = zone 3.
If the
ZONE_OFF
opcode is used in a program with temperature data = 50 and zone = 1, then a
temperature set point value in the following steps of 1700 would be sent to the middle and bottom as 1700
and the top as 1750.