for RS-485 slaves” is being used, HW4 automatically changes from 00 to 01 the RS-485 address
of any master that has slaves attached. As a result, all masters end up with the same RS-485
network address (01). In addition, HW4 automatically changes the RS-485 address of the slaves
in each multi-drop from 00 (factory default) to a unique address ranging from 02 to 64. The same
address range (02 to 64) is used again when there is more than one multi-drop RS485 network.

Notes:

- We recommend using HW4 to give each HygroClip DI a unique name for easier identification.
- In the situation where an RS-485 network is to be monitored by software other than HW4,

you will have to use HW4 to give each device a unique RS-485 address prior to connecting to
the network.

Example: HygroClip DI with USB port


The number of HygroClip DI with USB port that can be directly connected to a PC depends on the
number of USB ports available on the PC.














PC (HW4)

USB port

Master

Address 1

Address 2

Address 64

DI

USB

RS485

RS485

RS485

Slave

Slave

Multi-drop: up to 1000m (3300 ft)

RS485: 2 wires

IMPORTANT:

- If you change an instrument from master to slave, be sure to change the RS address of the

instrument to 00 before establishing the RS-485 connection. Not doing so may prevent HW4
from detecting the instrument. After detecting the instrument, HW4 will automatically change
the RS address to 02 or higher. Please note that HW4 may eventually change the address of
any master with address 00.

- All devices within a multi-drop should use the same Baud rate. See Baud rate compatibility

requirements.

- HygroClip DI-4 and DI-4-WL: please note that the Baud rate of the HygroClip DI and the

Baud rate of the internal Ethernet module should be set to the same value

- The RS485 wiring can be done with a twisted pair (2-wire, telephone type) and wall mounted

RJ45 receptacles. No shielded cable and no terminator should be required. Be sure to
observe the polarity for each connection. Using 4-wire cable, offers the option of powering all
devices in the multi-drop from a single DC voltage source.