Delta Electronics Programmable Logic Controller DVP-SS User Manual

24vdc

Advertising
background image

Warning

This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation &
wiring. Other detail infromation about programming and intructions is compatible with ES series; please see PLC
Application Manual. For more information about the optional peripherals, please see individual product instuction
shee or “DVP-PLC Application Manual: Special module”.

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the
enclosure, in order to prevent hazard to users or damage the PLC.

Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC.
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly
grounded

. Do NOT touch terminals when power on.

Introduction

Thank you for choosing Delta DVP-SS series programmable logic controller. DVP-SS provides MPU with 14
points, RUN/STOP switches and 8 ~ 16 points of extension. The maximum I/O points can reach 128 points.
DVP-SS can be used for various applications of different I/O points, power types, output modules and A/D,
D/A conversion. The power unit is separate from the MPU and is compact in size, plus easy to install.

Product Profile and Outline

90.00

4.00

3.00

25.20

60.00

1

2

3

4

5

6

7

8

9

3

10

11

12

13

ST OP

RU N

ER ROR

RU N

POW ER

X6

X7

C0

Y5

Y4

Y3

Y2

Y1

Y0

C2

C1

X5

X4

X3

X2

X1

X0

s

s

14

1. POWER, RUN, ERROR indicator

8. Extension port

2. I/O port for program communication (RS-232)

9. Extension unit clip

3. DIN rail clip

10. DIN rail (35mm)

4. I/O terminals

11. RS-485 communication port

5. I/O point indicator

12. Mounting rail for extension unit

6. Mounting hole for extension unit

13. DC power input

7. Nameplate

14. RUN/STOP switch

ENGLISH

Electrical Specifications

Model

Item

DVP14SS11R/T

Power supply voltage

MPU: 24V DC (-15%~20%) (With DC input reverse polarity protection)

Fuse

2A/250V AC

Power Consumption

3.5W

Insulation Resistance

> 5 M

Ω at 500 V DC (Between all inputs / outputs and earth)

Noise Immunity

ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m

Grounding

The diameter of grounding wire cannot be smaller than the wire diameter of
terminals L and N (All DVP units should be grounded directly to the ground pole).

Environment

Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2;
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

Vibration / Shock Resistance

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

Weight (approx.) (g)

214(g)/208(g)

Approvals

Input Point Electrical Specification

Input Type

DC (SINK or SOURCE)

Input Current

24V DC 5mA

Off → On,
X0, X1: 18.5V DC and above
X2 ~ X7: 16.5V DC and above

Active Level

On → Off,
X0 ~ X7: below 8V DC

Response Time

About 10ms (An adjustment range of 0 ~ 20ms could be selected through D1020 and
D1021)

Output Point Electrical Specification

Output Type

Relay-R

Transistor-T

Current Specification

1.5A/1 point (5A/COM)

55°C 0.1A/1point, 50°C 0.15A/1point
45°C 0.2A/1 point, 40°C 0.3A/1 point (2A/COM

Voltage Specification

Below 250V AC, 30V DC

30V DC

75VA (inductive)

Maximum Loading

90W (resistive)

9W/1 point

Response Time

About 10ms

Off

→On 20us

On

→Off 30us

Model Name & I/O Configuration

Input / Output

Input Unit

Output Unit

Model

Power

Point

Type

Point

Type

Profile reference

I/O Configuration

DVP14SS11R2

8

6

Relay

DVP14SS11T2

24V DC

8

DC Sink or

Source

6

Transistor

S/S

X0
X1
X2
X3
X4
X5
X6
X7

C0
Y0
C1

C2

Y1

Y2
Y3

Y5

Y4

Installation & Wiring

4.1 PLC Mounting Arrangements and Wiring Notes

DVP MPU

50m m
o r m o re

50m m

o r m o re

50 mm

o r m o re

50m m
o r m o re

Please install PLC in an enclosure with sufficient space around it to allow
heat dissipation as shown in the figure.

How to install DIN rail:

DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 7.5mm in depth. When
mounting PLC to DIN rail, be sure to use the end bracket to stop any side-to-side movement of PLC and reduce
the chance of wires being loosen. A small retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place
the clip onto the rail and gently push it up. To remove it, pull the retaining clip down and gently remove PLC from
DIN rail, as shown in the figure.

Wiring:

22-16AWG

<1.5mm

1. Use the 22-16AWG (1.5mm) single-core bare wire or the multi-core

wire for the I/O wiring, and the specifications of the terminal are
shown diagram on the left. The twisting power of the screw for the
PLC terminal is 1.95 kgf-cm (1.7 lb-in).

2. DO NOT place the input signal cable and output power cable in the

same wiring circuit.

3. Use only 60/75ºC copper conductor.

4.2 Wiring Notes

Environment

1. DO NOT store the PLC in an atmosphere that is dusty, smoky, with metallic debris or corrosive or flammable

gases.

2. DO NOT store the PLC in an environment with high temperature or high humidity.

3. DO NOT install the PLC on a shelf or on an unstable surface.

Power Input Wiring

DVP-SS uses DC input power. Therefore, make sure that DVP-SS is connected to terminals 24V DC and 0V
(power range 20.4 ~ 28.8V DC) when the power is ON. DVP-SS will stop the operation and the output will be
OFF whenever the power input is lower than 20.4V DC. Consequently, the ERROR LED will blink swiftly.

S/S

X0

X1

X2

+24 V 24 G

OV

24V DC

DC/DC

2.5 A

5V

20.4VDC~28.8VDC

Safety Wiring

Since a PLC controls many devices, actions of any device may affect actions of other devices, and the
breakdown of any one device may cause the breakdown of the whole auto-control system and danger.
Therefore, we suggest you wire a protection circuit at the power input terminal, as shown in the figure below.

AC power supply load

Power circuit protection fuse (2A)

Power indicator

Emergency stop

This button can cut off the system power supply when
accidental emergency takes place.

System circuit isolation device

The device is made of electromagnetic contactor and relay
as the switch to prevent the instability of system when the
power is intermittently supplied.

DVPPS01/24V DC power module

DVP-PLC

MC

MC

1

2

3

L

N

5

4

1

24V

0V

8

Guard

Lim it

6

7

24V 0V

Power supply: 24V DC

Input Point Wiring

There are two types of DC inputs, SINK and SOURCE.

Two types of DC wiring are used: SINK and SOURCE, defined as follows:

Sink = common port for current input S/S

Source = common port for current output S/S

Sin k ing

S/S

X0

Sourcing

S/S

X0

Input point loop equivalent circuit

Wiring loop

DC Type

(DC Signal IN)

SINK Mode

24VDC

0V

X0

S/S

+24V

SINK

+ 5V

OV

S/S

X0 X1 X2

+24V

Sink Type

24VDC

Input point loop equivalent circuit

Wiring loop

DC Type

(DC Signal IN)

SOURCE Mode

24VDC

0V

X0

S/ S

+24 V

S OURCE

+5 V

0V

S/S

X0

X1

X2

+24V

Source Type

24VDC

Output Point Wiring

Every output contact possesses a overload capacity that is twice as much as the rated current for 5
minutes. The exceeded range may result in contact malfunction and even the burn-down of internal
circuit.

Y0

RY

LED

C0

LOAD

P OWER

DVP-**-**-11-R

RELAY OUTPUT

DVP-**-**-11-T

TRANSISTOR OUTPUT

LED

Y0

C0

LOAD

< 0.3A

T
R
G

1. Two types of DVP-SS series PLC output modules: Relay or Transistor. For the electrical specification,

please refer to the function specification.

2. Please watch out the connection of common terminals while wire the outputs. For example, when

wiring DVP14SS11R, output terminal Y0 uses one common terminal C0, Y1 uses C1, and Y2 ~ Y5
share C2, as shown below:

C0 Y0 C1 Y1 C2 Y2 Y3 Y4 Y5

Action indication: When the output point is active, the corresponding indicator at the front panel will be
on.

3. Isolated circuit: The optical coupler is used to isolate signals between PLC internal circuits and input

modules.

注意事項

本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與 ES 系列
相容,詳細說明請見 DVP-PLC 應用技術手冊【程式篇】

,選購之週邊裝置詳細說明請見該產品隨機手冊。

本機為開放型(OPEN TYPE)機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/

衝擊意外之外殼配線箱內。另必須具備保護措施 (如: 特殊之工具或鑰匙才可打開) 防止非維護人員操

作或意外衝擊本體,造成危險及損壞。

交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請
勿在上電時觸摸任何端子。本體上之接地端子

務必正確的接地,可提高產品抗雜訊能力。

產品簡介

謝謝您採用台達 DVP 系列可程式控制器。DVP-SS 系列提供 14 點數的主機,俱備 RUN/STOP 開關及 8 ~ 16
點擴充機,最大輸入/輸出擴充分別可達 128 點。另依輸入/輸出點數、電源、輸出模組及類比/數位轉換(A/D,
D/A

轉換)等具各類機型,滿足各種應用場合。電源單元與主機分離,體積小,安裝容易。

產品外觀及各部介紹

90.00

4.00

3.00

25.20

60.00

1

2

3

4

5

6

7

8

9

3

10

11

12

13

STOP

RU N

ER RO R

RU N

POW ER

X6

X7

C0

Y5

Y4

Y3

Y2

Y1

Y0

C2

C1

X5

X4

X3

X2

X1

X0

s

s

14

1.

電源、運行及錯誤指示燈

8.

擴充機連接口

2.

程式通訊輸出/入口 (RS-232)

9.

擴充機固定扣

3. DIN

軌固定扣

10. DIN

軌糟 (35mm)

4.

輸出/入端子

11. RS-485

通訊口

5.

輸出/入點指示燈

12.

擴充機固定槽

6.

擴充機定位孔

13.

電源輸入口

7.

銘牌

14. RUN/STOP

開關

繁體中文

繁體中文

繁體中文

繁體中文

電氣規格

機種

項目

DVP14SS11R/T

電源電壓

24V DC (-15% ~ 20%)

(具直流輸入電源極性反接保護)

動作規格

電源瞬間斷電 5ms 以內繼續運轉

電源保險絲容量

2A/250V AC

消耗電力

3.5W

絕緣阻抗

5 MΩ

以上(所有輸出/入點對地之間 500V DC)

雜訊免疫力

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

接地

接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地)

操作/儲存環境

操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級 2
儲存:-40°C ~ 70°C(溫度),5 ~ 95%(濕度)

耐振動/衝擊

國際標準規範 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

重量(約,g)

214 (g)/208 (g)

輸入點電氣規格

輸入形式

直流(SINK 或 SOURCE)

輸入電流

24VDC 5mA

Off → On,
X0

、X1 為 18.5V DC 以上

X2 ~ X7

為 16.5V DC 以上

動作位準

On → Off,
X0 ~ X7

為 8V DC 以下

反應時間

約 10 ms(由 D1020 及 D1021 可作 0 ~ 20ms 的調整)

輸出點電氣規格

輸出點形式

繼電器-R

電晶體-T

電流規格

1.5A/1

點(5A/COM)

55°C 0.1A/1

點、50°C 0.15A/1 點

45°C 0.2A/1

點、40°C 0.3A/1 點(2A/COM)

電壓規格

250VAC,30VDC

以下

30V DC

75VA

(電感性)

最大負載

90 W

(電阻性)

9W/1

反應時間

約 10 ms

Off → On 15us
On → Off 25us

Advertising