INSTALLATION

Continued

Figure 14 - External Regulator With Vent

Pointing Down

External Regulator

Propane/LP
Supply Tank

Vent
Pointing
Down

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test Gauge Connection*

3/8" NPT
Pipe Nipple

Heater
Cabinet

Equipment
Shutoff
Valve *

3" Min.

From External
Regulator
(11" W.C. to
14" W.C.
Pressure)

Ground Joint
Union

Tee Joint

Pipe
Nipple

Cap

Sediment Trap

Figure 15 - Gas Connection

Pressure
Regulator

* A CSA design-certified equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certified equipment shutoff valve from your
dealer. See Accessories, page 25.

CONNECTING TO GAS SUPPLY

WARNING: This appliance

requires a 3/8" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.

WARNING: A qualified ser-

vice person must connect heater
to gas supply. Follow all local
codes.

CAUTION: Never connect

heater directly to the propane/
LP supply. This heater requires
an external regulator (not sup-
plied). Install the external regu-
lator between the heater and pro-
pane/LP supply.

The installer must supply an external regulator.
The external regulator will reduce incoming gas
pressure. You must reduce incoming gas pressure
to between 11 and 14 inches of water. If you do
not reduce incoming gas pressure, heater regula-
tor damage could occur. Install the external regu-
lator with the vent pointing down as shown in Fig-
ure 14. Pointing the vent down protects it from
freezing rain or sleet.

CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
large enough diameter to allow
proper gas volume to heater. If
pipe is too small, undue loss of
volume will occur.

Typical Inlet Pipe Diameters

GMP20PT, GMP16(T) - 3/8" or greater

GMP30BT, GMP26(T) - 1/2" or greater

Installation must include equipment shutoff valve,
union, and plugged 1/8" NPT tap. Locate NPT tap
within reach for test gauge hook up. NPT tap must
be upstream from heater (see Figure 15).
IMPORTANT:

Install an equipment shutoff valve

in an accessible location. The equipment shutoff
valve is for turning on or shutting off the gas to
the appliance.