Rs-485 communications – WattMaster WCC III part 10 User Manual

Page 12

Advertising
background image

10. RS-485 COMMUNICATIONS

WCC III Technical Guide

10-10

SAT III Troubleshooting with a Digital Voltmeter

SAT III Communications Troubleshooting with a Digital Voltmeter

The voltage measurements in Figure 10-9 are approximate voltages. These voltage measurements are taken when the power to the SAT
III Controller is “ON” and the RS-485 SAT communications loop is connected. These two voltages will fl uctuate slightly and also will
momentarily “fl ip” to the other meter reading’s value. The voltage measurement from “T” to “SHIELD” should be around 2.7 VDC. The
voltage measurement from “R” to “SHIELD” should be around 3.00 VDC. Typical bad voltage measurement values would be anything
above 3.8 VDC and anything below 1.5 VDC. Helpful hint: Removal of the SAT III cover may aid in measuring the communication loop
voltages.

Figure 10-9: Typical SAT III RS-485 Satellite Communications DC Voltage Measurements with the Loop

Connected

Figure 10-10: Typical SAT III RS-485 Satellite Communications DC Voltage Measurements with the Loop

Disconnected

The voltage measurements in Figure 10-10 are approximate voltages. These voltage measurements are taken when the power to the SAT
III Controller is “ON” and the RS-485 SAT communications loop is disconnected. These two voltages will not fl uctuate. The voltage
measurement from “T” to “SHIELD” should be around 3.25 VDC. The voltage measurement from “R” to “SHIELD” should be around
3.25 VDC. Typical bad voltage measurement values would be anything above 3.8 VDC and anything below 1.5 VDC. Helpful hint:
Removal of the SAT III cover may aid in measuring the communication loop voltages.