Set up of master ports
set up of the master ports is possible using a sND_uD command, CI = 51 (hex)
with the following data field.

Data field

DIF = 01 (hex) VIF = FD (hex) VIFE = E2 (hex) VIFE = 00 (hex) DATA

Description 8-bit integer

Ext. coding

Cont. signal

Write replace

Port setup

The DATA is coded according the following:

Value

Master RS-232 port

Master M-Bus port

00 (hex)

Inactive

Inactive

01 (hex)

Inactive

Active

02 (hex)

Active

Inactive

03 (hex)

Active

Active

Read out of master ports
Read out of the master ports setting is possible using a REQ_uD2 command.
AD-01 will respond with a RsP_uD, CI=72 (hex) with the following data field.

Data field

DIF = 01 (hex) VIF = FD (hex) VIFE = E2 (hex) DATA

Description 8-bit integer

Ext. coding

Cont. signal

Port setup

The DATA is coded according the following:

Value

Master RS-232 port

Master M-Bus port

00 (hex)

Inactive

Inactive

01 (hex)

Inactive

Active

02 (hex)

Active

Inactive

03 (hex)

Active

Active

Error indication
AD-01 includes possibilities to alert the supervision system of short-circuit or overload
on the M-Bus master interface. Readout of error status can be made using a REQ_uD2
command. AD-01 uses the status field in a RsP_uD answer sequence to alert possible
errors.
The coding of the status field is according to the following:

Value status field

Description

00 (hex)

No error

10 (hex)

Overload / short-circuit of
M-Bus master interface