Eaton Electrical -66103 User Manual

Page 12

Advertising
background image

12 - 34003906EN/AE

Configuration of the JBUS/MODBUS communication parameters

Use the cord supplied with the card

Connect the card to a computer

Use a terminal emulator such as HyperTerminal

TM

with these settings

"Echo typed characters locally" option: disabled

Check that UPS power is on.

Type EATON (or eaton).

The main configuration menu is displayed:

Press the 5 key (Jbus configuration).

The Jbus configuration menu is displayed:

Through settings port

Bits per second

Data bits

Stop bits

Parity

Flow control

9600

8

1

none

none

EATON
NETWORK MANAGEMENT CARD

1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit

Jbus settings

1 : Display Jbus settings
2 : Modify Jbus settings
3 : Display Jbus diagnostics
4 : Reset Jbus diagnostics
5 : Return to Jbus Default Configuration
6 : Display Jbus frames
0 : Exit

66102

Settings/Sensor

ETHERNET

100M

10M

UPS data

RS232

On = Lin

k

Blink = A

ct

ETHERNET

66103

UPS data

RS232

100M

10M

Connect the RS232 link to a

terminal

(Microsoft Hyper terminal)