The Network Management Card & Modbus/Jbus (66103) can be hot-plugged on all UPSs from
EATON equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart
the UPS.

●

Remove the plastic cover of the Minislot.

●

Note the MAC address of the card before inserting it.

●

Insert and secure the card with the screws.

●

Connect the ETHERNET cable.

●

Check the ETHERNET port indications.

●

Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has

terminated correctly.

Note. Connection detection continues until the card has been connected to the network. Once
connection is made, card start-up continues.

Once the card has started, proceed as indicated below.

●

Connect the serial cable to card’s service port and PC’s COM port

●

Use a terminal emulator such as HyperTerminal

TM

with these settings

"Echo typed characters locally" option: disabled

●

Type EATON (or eaton).

The main configuration menu is displayed:

IP SETTINGS

Bits per second

Data bits

Stop bits

Parity

Flow control

9600

8

1

none

none

EATON
NETWORK MANAGEMENT CARD

1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit