Lightning protection, Rack-mounting – H3C Technologies H3C MSR 2600 User Manual

Page 11

Advertising
background image

4

•

Capacitive coupling

•

Inductive coupling

•

Radiative coupling

•

Common impedance coupling

•

Conductive coupling

To prevent EMI, take the following actions:

•

Take measures against interference from the power grid.

•

Do not use the router together with the grounding equipment or lightning-prevention equipment of
power equipment, and keep the router far away from them.

•

Keep the router far away from high-power radio launchers, radars, and equipment with high
frequency or high current.

•

Use electromagnetic shielding when necessary.

Lightning protection

To better protect the router from lightning, do as follows:

•

Make sure the grounding cable of the chassis is correctly grounded.

•

Make sure the grounding terminal of the AC power receptacle is correctly grounded.

•

Install a lightning arrester at the input end of the power supply to enhance the lightning protection
capability of the power supply.

•

Install a special lightning arrester at the input end of outdoor signal lines (for example, E1/T1 line)
to which interface modules of the router are connected to enhance the lightning protection

capability.

Rack-mounting

Before mounting the router in a rack, adhere to the following requirements:

•

The rack is equipped with a good ventilation system.

•

The rack is sturdy enough to support the router and its accessories.

•

For heat dissipation and device maintenance, make sure the front and rear of the rack are at least
0.8 m (2.62 ft) away from walls or other devices, and the headroom in the equipment room is no

less than 3 m (9.84 ft).